Date |
Text |
2019-04-01 12:38:57 | GAS 1ST REVIEW**DENIED** |
| |
| 1) PROVIDE TANKLESS WATER HEATER COMPLETE INSTALLATION |
| MANUAL. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / |
| INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY |
| COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017 |
| FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED |
| AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS |
| APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF |
| INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1 |
| |
| 2) PROVIDE DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN |
| RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER |
| HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND |
| DRAWN. WPB AMEND. TO FBC SEC. 107.2.1. |
| |
| 3) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| INSTALLATION. 2014 FGC SEC.410.1, 2017 FBC-RES. SEC. |
| G2421.1. |
| |
| 4) PROVIDE SHUT OFF VALVE AND SEDIMENT TRAP AT THE |
| TANKLESS. FBC G 409.5.1, 408.4 |
| |
| 5) THE PLANS INDICATE AN EXISTING GAS METER. THE BTU |
| LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE |
| TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING |
| SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING |
| SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING |
| SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS |
| THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH |
| APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH |
| APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF |
| PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE |
| OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE |
| EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE |
| SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE |
| REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES. |
| FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR |
| SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3. |
| |
| 6) SIZING TABLE CALLED OUT 402.4(2) ON P-003 LIST MAX |
| BTU @ 20' AS 118,000 BTU'S. YOUR PROPOSED 1/2" SCH 40 |
| METAL PIPE WOULD BE UNDERSIZED FOR 150000 BTU'S. TOTAL |
| MUST INCLUDE THE VERTICAL PIPING IN DISTANCE. |
| |
| TIM HUNT |
| PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR |
| CITY OF WEST PALM BEACH |
| 561-248-2703 |
| [email protected] |
| |