2019-04-01 14:20:41THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET T 1 - THERE ARE INDICATIONS OF FIRE SPRINKLER
 AND FIRE ALARM NOTES WITH WORK UNDER SEPARATE SHOP
 DRAWINGS; HOWEVER, NOTHING ABOUT MAINTAINING EITHER
 SYSTEMS WHILE UNDER DEMO & CONSTRUCTION.
  
 THE FS AND FA SYSTEMS SHALL REMAIN FUNCTIONAL AND BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION.
  
 PLEASE ENSURE AND PROVIDE AN APPLICABLE NOTE OF
 ACKNOWLEDGEMENT.
  
  
  
 2) SHEETS A 1 & A 3 - DOOR 01 SWINGS OUT INTO THE EXIT
 CORRIDOR WHICH DOES NOT APPEAR TO ENCROACH INTO THE
 REQUIRED EGRESS WIDTH: HOWEVER, THE DOOR SWINGS AT 90'.
  
 PER NFPA 101 THE DOOR IS REQUIRED TO SWING 180'
  
 7.2.1.4.3* DOOR LEAF ENCROACHMENT.
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS
 SHALL LEAVE NOT LESS THAN ONE-HALF OF THE REQUIRED
 WIDTH OF AN AISLE,
 A CORRIDOR, A PASSAGEWAY, OR A LANDING UNOBSTRUCTED,
 UNLESS BOTH
 OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING
 BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENT OF
 7.2.1.4.3.2.
 7.2.1.4.3.2 WHEN FULLY OPEN, ANY DOOR LEAF IN A MEANS
 OF EGRESS
 SHALL NOT PROJECT MORE THAN 7 IN. (180 MM) INTO THE
 REQUIRED WIDTH
 OF AN AISLE, A CORRIDOR, A PASSAGEWAY, OR A LANDING,
 UNLESS THE DOOR
 LEAF IS EQUIPPED WITH AN APPROVED SELF-CLOSING DEVICE
 AND IS NOT
 REQUIRED BY THE PROVISIONS OF 7.2.1.4.2 TO SWING IN THE
 DIRECTION OF
 EGRESS TRAVEL.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
  
 3) SHEET A 3 - THERE IS AN INDICATION THAT DOOR 02
 HARDWARE AS HAVING A KEY. THIS DOOR IS INDICATED AS AN
 EXIT DOOR.
  
 PER NFPA 101 CH 38 & 7
  
 38.2.2.2 DOORS.
 38.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
 38.2.2.2.2* LOCKS COMPLYING WITH 7.2.1.5.5 SHALL BE
 PERMITTED
 ONLY ON PRINCIPAL ENTRANCE/EXIT DOORS.
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM
 THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED.
 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY
 TO DOOR
 LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER EXPOSURE TO
 ELEVATED
 TEMPERATURE IN ACCORDANCE WITH THE LISTING, BASED ON
 LABORATORY
 FIRE TEST PROCEDURES.
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A
 TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM
 THE EGRESS
 SIDE.
 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3
 SHALL NOT
 APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18 THROUGH
 23.
  
 PLEASE PROVIDE DETAILS IN COMPLIANCE.
  
  
  
 4) SHEET A 3 - THERE IS AN INDICATION THAT DOOR 01
 HARDWARE AS HAVING A KEY AND DEADBOLT. THIS DOOR IS
 INDICATED AS AN EXIT DOOR.
  
 PER NFPA 101 CH 38 & 7
  
 38.2.2.2 DOORS.
 38.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
 38.2.2.2.2* LOCKS COMPLYING WITH 7.2.1.5.5 SHALL BE
 PERMITTED
 ONLY ON PRINCIPAL ENTRANCE/EXIT DOORS.
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM
 THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED.
 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY
 TO DOOR
 LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER EXPOSURE TO
 ELEVATED
 TEMPERATURE IN ACCORDANCE WITH THE LISTING, BASED ON
 LABORATORY
 FIRE TEST PROCEDURES.
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A
 TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM
 THE EGRESS
 SIDE.
 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3
 SHALL NOT
 APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18 THROUGH
 23.
  
 PLEASE PROVIDE DETAILS IN COMPLIANCE.
  
  
  
 5) SHEET LS 1 & A 4 - DOOR 04 IS INDICATED AS AN EXIT
 THAT IS LEADING TO AN AREA AS FUTURE EXPANSION.
  
 HOW WILL THIS EXIT BE CONTROLLED AND MAINTAINED AND
 FUNCTION AS AN EXIT?
  
 PLEASE PROVIDE DETAILS
  
  
  
 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL