Plan Review Notes For Permit 19030514 |
Permit Number |
19030514 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-03-27 14:17:23 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THE SITE PLAN INDICATES THE FENCE BLOCKING THE | | ROASDWAY. | | | | THE TRAVLE PATH APPEARS TO BE A FIRE LANE AROUND THE | | BUILDING AND CANNOT BE BLOCKED, | | | | PLEASE MOVE THE FENCE OUT OF THE VEHILCE TRAVEL PATH OR | | PROVIDE A FULL SITE PLAN SHOWING ALL ACCESS POINTS TO | | THE BUILDING | | FOR CONSIDERATION TO BLOCK THE VEHICLE TRAVEL PATH. | | | | | | | | 2) NO GATES/DOORS ARE LOCATED ALONG THE FENCE LINE. | | | | PLEASE PROVIDE A DOOR/GATE ALONG THE CURRENT ACCESS | | POINT OF THE GENERATOR. | | | | | | | | 3) WHAT IS THE PURPOSE FOR THE FENCE? | | | | | | | | | | 4) HOW LONG WILL THE FENCE BE INSTALLED? | | | | | | | | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | | | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|