2019-03-14 08:20:01 | BUILDING PLAN REVIEW |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| BUILDING PLANS EXAMINER, PX3169 |
| 1&2 FAMILY PLANS EXAMINER, SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 1ST REVIEW |
| RESULTS: DENIED |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| FLOORING |
| |
| TWO COMPLETE COLLATED SETS OF ALL DOCUMENTS REQUIRED |
| |
| PLEASE NOTE THAT TEST REPORTS ARE REQUIRED - |
| MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO |
| DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST |
| REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE |
| MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) |
| |
| A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. |
| THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM |
| CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| |
| B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| ASTM E 492. |
| |
| THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM |
| CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| |
| |
| THE FOLLOWING INFORMATION IS REQUIRED FOR ALL FLOORING |
| SUBMITTALS: |
| |
| 1. TOTAL SQUARE FOOTAGE OF NEW FLOORING. |
| 2. TYPE OF PROPOSED FLOORING |
| (TILE/MARBLE/LAMINATE/WOOD/OTHER). |
| 3. STATED VALUE OF WORK. |
| 4. EXISTING SITE CONDITIONS: |
| A) THICKNESS OF SLAB. B) CEILING ASSEMBLY (OPEN |
| CONCRETE/SUSPENDED GYPSUM/ACOUSTICAL) |
| 6. PROPOSED UNDERLAYMENT. |
| 7. TEST REPORTS FOR PROPOSED UNDERLAYMENT BASED ON |
| EXISTING SITE CONDITIONS. |
| 8. TEST REPORTS MAY BE BASED ON THE FOLLOWING ASTM?S, |
| E-84, E-90 & E-492. |
| 9. ALL DOCUMENTS SHALL BE SUBMITTED IN DUPLICATE. |
| |
| FBC 1207.2 AIR-BORNE SOUND. ASTM E ? 90-04 |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E 90. |
| |
| FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E ? 492-09 |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC SPACE OR SERVICE |
| AREA WITHIN THE STRUCTURE SHALL HAVE AN IMPACT |
| INSULATION CLASS (IIC) RATING OF NOT LESS THAN 50 (45 |
| IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E |
| 492. |
| |
| FBC 603.1 FLAME SPREAD |
| FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| OR UL 723 |
| FBC 804.4.1 TEST REQUIREMENT. |
| IN ALL OCCUPANCIES, INTERIOR FLOOR COVERING MATERIALS |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE DOC FF-1 |
| ?PILL TEST? (CPSC 16 CFR PART 1630) OR WITH ASTM D2859 |
| |
| |
| |