2019-11-19 08:51:13 | ***CORRECTIONS*** | | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | FBC M = FBC MECHANICAL | | | | 3RD BUILDING REVIEW DENIED: | | | | 1. OK | | 2. OK | | 3, 4, 5. OK | | 6, 7, 8. OK/APPROVED WITH PROVISO, FBC B 107.3.4.1 | | PROVIDE DEFERRED SUBMITTALS PRIOR TO ROOF WORK. | | 9.OK | | 10. N/R | | | | PROVISO: | | | | ADDED TO PAGE S-3. | | AWS D1.1 CLAUSE 3.1: AT TIME OF INSPECTION PLEASE | | PROVIDE A WELD PROCEDURE SPECIFICATION; THE W.P.S. | | SPECIFIES THE REQUIRED ESSENTIAL VARIABLES INCLUDING: | | BASE MATERIALS, JOINTS, PROCESS, AND FILLER METALS TO | | BE USED. | | AWS D1.1 CLAUSE 4.15: AT TIME OF INSPECTION PLEASE | | PROVIDE A WELDER PERFORMANCE QUALIFICATION RECORD; THE | | W.P.Q.R. PROVIDES INFORMATION WHICH CAN BE USED TO | | VERIFY THE WELDER?S QUALIFICATION AND CERTIFICATION AS | | IT RELATES TO THE WELDING REQUIREMENTS OF THE PROJECT. | | |
|