Plan Review Notes
Plan Review Notes For Permit 19030479
Permit Number 19030479
Review Stop M
Sequence Number 2
Notes
Date Text
2019-04-25 16:30:291ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19030479
 4/25/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOE THE
 NEW SYSTEMS IN ACCORDANCE WITH SECTION C403.2.1 FBC EC.
  
 2) PROVIDE AUTOMATICALLY CONTROLLED SHUTOFF DAMPERS FOR
 THE O/A INTAKES- SECTION C403.2.4.3 FBC-EC.
  
 3) REFER TO SECTION 301.16 FBC M: THE PROPOSED BUILDING
 IS IN A FLOOD ZONE. PLEASE CONSULT WITH THE ARCHITECT
 OF RECORD FOR BASE FLOOD ELEVATION HEIGHT, AND VERIFY
 THE BARD UNITS WILL BE INSTALLED AT OR ABOVE THAT
 HEIGHT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved