2019-08-20 11:10:55 | BUILDING REVIEW APPROVED WITH PROVISO: | | 1- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH SEC. | | R401.3 FBC-RESIDENTIAL. SEC. 107.2.5 CITY AMENDMENTS | | AND SEC. 110.9 CITY AMENDMENTS. | | 2- ENGINEER OF RECORD TO SPECIFY ROOF TILE FASTENING AS | | REQUIRED BY SEC. 107.2.1.1 CITY AMENDMENTS. IF | | SPECIFYING ROOF TILE ADHESIVE, THEN NEED PRODUCT | | APPROVAL. IF SPECIFYING SCREWS, THEN SPECIFY SCREW SIZE | | AND NUMBER OF SCREWS. | | 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | FAC 61G20-3.001 FOR: | | A)WINDOW MULLIONS AND SPECIFY MULLION SIZE. | | B) ROOF TILE ADHESIVE IF SPECIFIED BY THE ENGINEER OF | | RECORD. AND CLEARLY MARK PADDY SIZE. | | C) DOUBLE DOORS AS SHOWN FOR NEW STORAGE. | | D) RIDGE VENT SPECIFIED BY THE ENGINEER OF RECORD ON | | PAGE 9.0 OF DRAWINGS SUBMITTED. | | 4- NEW ENGINEER OF RECORD TO REVIEW AND APPROVE IN | | WRITING ALL PRODUCT APPROVALS AS REQUIRED BY SEC. | | 107.3.4.1 CITY AMENDMENTS. | | 5- ENGINEER OF RECORD SPECIFIES RIDGE VENT. SEE ATTIC | | SPACE VENTILATION CALCULATIONS ON PAGE 9.0. ENGINEER TO | | PROVIDE DETAILS/SPECIFICATIONS SHOWING HOW PROVIDING | | THE RIDGE VENT VENTILATION. SEC. 107.2.1 CITY | | AMENDMENTS. | | |
|