2019-06-17 08:19:38 | PLUMBING 2ND REVIEW**DENIED**FL ST 553.80 (B)2B WITH |
| RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? |
| DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| |
| |
| 1) 2ND REQUEST.PROVIDE WATER HEATER INSTALLATION |
| MANUAL/ SPEC SHOWING THE EFFICIENCY RATING OF E.F .97 |
| AS CALLED OUT IN THE R405 FORM. FBC 107.2.1. |
| |
| 2) 2ND REQUEST. PROVIDE A SHOWER DETAIL AND PROVIDE |
| WHAT SHOWER PAN MATERIAL IS BEING USED. FBC 107.2.1 |
| (A) FLOOR SHALL BE PRE-PITCH @ MIN 2% BEFORE SHOWER PAN |
| MATERIAL IS INSTALLED. YOUR DETAIL ONLY SHOWS THE |
| ACTUAL TILE BEING PITCHED @ 2%. FBC-R P2709.3 |
| |
| 3) 2ND REQUEST. PLUMBING ISOMETRIC DRAWING PROVIDE ON |
| SHT. 7.1 HAS THE WASHING MACHINE AND LAUNDRY TUB |
| DISCHARGING INTO THE BATHROOM GROUP WET VENT. FIXTURES |
| OUTSIDE OF THE BATHROOM GROUP ARE NOT PERMITTED TO |
| DISCHARGE INTO THE BATHROOM GROUPS HORIZONTAL WET VENT |
| AND SHALL DISCHARGE DOWNSTREAM OF THE BATHROM GROUP. |
| FBC-R P3108.1 |
| |
| 4) ALL SHEETS SHALL BE SIGN AND SEALED. F.S 471,481, |
| |
| |
| TIM HUNT |
| PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR |
| CITY OF WEST PALM BEACH |
| 561-248-2703 |
| THUNT@CGA SOLUTIONS.COM |
| |
| |