Date |
Text |
2019-06-20 16:43:57 | RESIDENTIAL (R3) ADDITION/ALTERATION SECOND BUILDING |
| REVIEW CHECKLIST. |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| |
| NOTE: |
| BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER |
| THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID |
| CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR |
| TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME |
| OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT |
| ISSUANCE. |
| ****NEED ENERGY CALCULATIONS TO BE PROPERLY SIGNED BY |
| THE OWNER AND ALL PLANS NEED THE ENGINEER'S SEAL AND |
| SIGNATURE BEFORE APPROVAL. |
| |
| |
| |
| ORIGINAL COMMENT: |
| 1- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE |
| FOLLOWING: |
| SEC. R401.3 FBC-RESIDENTIAL (DRAINAGE). |
| SEC. 107.2.5 CITY AMENDMENTS (SITE PLAN). |
| SEC. 110.9 CITY AMENDMENTS (IMPACT OF CONSTRUCTION). |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED. |
| |
| 2- OK. |
| |
| 3-OK |
| |
| ORIGINAL COMMENT: |
| 4- A)DESIGN PRESSURES SHOWN FOR NEW MASTER BEDROOM |
| DOUBLE DOORS AND NEW FAMILY ROOM SINGLE DOOR DON'T |
| CORRESPOND TO THE EFFECTIVE WIND AREA SHOWN ON |
| COMPONENTS AND CLADDING DESIGN PRESSURES ON SHEET 5.1. |
| REVISE AS REQUIRED. SEE SIZE OF DOORS AND REVISE AS |
| REQUIRED. |
| |
| RESPONSE: |
| PARTIALLY ADDRESSED. THE DOUBLE DOORS ARE CORRECT BUT |
| SINGLE DOOR IS NOT. THE LOADS FOR SINGLE DOOR "01" NEED |
| TO BE REVISED. NEED TO USE DESIGN PRESSURES FOR THE |
| LOWER EFFECTIVE AREA AS REQUIRED BY FOOTNOTE "B" OF |
| TABLE R301.2(2)FBC-RESIDENTIAL. SEE TABLE FOR DESIGN |
| PRESSURES OF 20S.F. EFFECTIVE WIND AREA AND REVISE AS |
| REQUIRED. REMEMBER THAT DESIGN PRESSURES ON THIS TABLE |
| NEED TO BE ADJUSTED WITH THE EXPOSURE AND HEIGHT |
| COEFFICIENT OF TABLE R301.2(3) FBC-RESIDENTIAL. |
| |
| ORIGINAL COMMENT: |
| B) GARAGE DOORS DESIGN PRESSURES SHOWN ON THE |
| COMPONENTS AND CLADDING DESIGN PRESSURES ON SHEET 5.1 |
| DON'T CORRESPOND TO THE ONES SHOWN ON TABLE 301.2(4) |
| FBC-RESIDENTIAL WHEN MULTIPLIED BY THE COEFFICIENT FOR |
| EXPOSURE "C". SEE TABLE R301.2(3) FBC-RESIDENTIAL AND |
| REVISE AS REQUIRED. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED. |
| |
| 5- ENERGY CALCULATIONS SUBMITTED: |
| ORIGINAL COMMENT: |
| A) THE ENERGY FORM R405-2017 IS REQUIRED TO BE |
| CERTIFIED AT THE BOTTOM BY THE OWNER OR OWNER'S LEGALLY |
| DESIGNATED AGENT AS REQUIRED BY SEC. R103.1.1.2 |
| FBC-ENERGY CONSERVATION, 6TH EDITION (2017). |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED. |
| |
| B)OK. |
| |
| C) OK. |
| |
| D) OK. |
| |
| E) OK. |
| |
| ORIGINAL COMMENT: |
| 6- ENGINEER OF RECORD TO SPECIFY ROOF TILE FASTENING IN |
| THE CONSTRUCTION DOCUMENTS. SEC. 107.2.1.1 CITY |
| AMENDMENTS. IF SPECIFYING ROOF TILE ADHESIVE, THEN |
| SPECIFY PADDY SIZE AND PROVIDE PRODUCT APPROVAL. IF |
| SPECIFYING SCREWS, THEN SPECIFY SCREW SIZE AND NUMBER |
| OF SCREWS. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED. |
| |
| 7-PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.001 FOR: |
| (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| SUBMITTAL. CONTRACTOR TO ADVICE IF SUBMITTING THIS |
| INFORMATION LATER). |
| |
| ORIGINAL COMMENT: |
| A)WINDOW MULLIONS AS SHOWN ON PLANS. AND REQUIRED: |
| CLEARLY SPECIFY MULLION SIZE TO BE USED TO VERIFY |
| COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED. |
| |
| ORIGINAL COMMENT: |
| B)FIXED WINDOWS. PROVIDE FLORIDA PRODUCT APPROVAL COVER |
| PAGE THAT CORRESPONDS TO DRAWINGS SUBMITTED. COVER PAGE |
| SUBMITTED IS FOR MANY DIFFERENT PRODUCT APPROVAL |
| NUMBERS. UNABLE TO IDENTIFY THE ONE THAT CORRESPONDS TO |
| DRAWING SUBMITTED. |
| |
| RESPONSE: |
| PARTIALLY DONE. PROVIDE COMPLETE INFORMATION. PROVIDE |
| FLORIDA PRODUCT APPROVAL COVER PAGE THAT CORRESPONDS TO |
| DRAWINGS SUBMITTED. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| ORIGINAL COMMENT: |
| C) ROOF TILE ADHESIVE IF SPECIFIED BY THE ENGINEER OF |
| RECORD. SEE ROOF TILE NOA SUBMITTED FOR LISTED |
| ADHESIVES. AND CLEARLY MARK PADDY SIZE AS REQUIRED BY |
| CITY POLICY FOR ALL ROOFING PERMITS. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED. |
| |
| ORIGINAL COMMENT: |
| D) DOUBLE DOORS AS SHOWN FOR NEW STORAGE. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED. |
| |
| 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| ABOVE PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1 |
| CITY AMENDMENTS |
| |
| 9- OK. |
| |
| 10- OK. |
| |
| NEW COMMENT: |
| 11- ALL PLANS ON BOTH SETS NEED TO HAVE THE SEAL AND |
| SIGNATURE OF THE ENGINEER OF RECORD AS REQUIRED BY |
| CHAPTER 471 F.S. WHEN SUBMITTING PLANS/DOCUMENTS FOR |
| PUBLIC RECORDS. |
| |
| |
| 12- WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND |
| REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. |
| PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD |
| DRAWINGS/DOCUMENTS FOR REFERENCE. |
| |
| RESPONSE: |
| ORIGINAL PLANS AND SUBMITTALS (ENERGY CALCULATIONS) |
| WERE NOT RE-SUBMITTED. IN THE FUTURE PLEASE RES-SUBMIT |
| EVERYTHING THAT WAS REVIEWED IN ORDER TO USE THEM FOR |
| REFERENCE AND EXPEDITE THE REVIEW PROCESS. |
| |
| EVEN THOUGH RESPONSE LETTER IS NOT MANDATORY IT IT'S |
| VERY HELPFUL TO PROVIDE ONE IN ORDER TO TO EXPEDITE THE |
| REVIEW PROCESS. |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| |