Plan Review Notes
Plan Review Notes For Permit 19030429
Permit Number 19030429
Review Stop B
Sequence Number 2
Notes
Date Text
2019-06-20 16:43:57RESIDENTIAL (R3) ADDITION/ALTERATION SECOND BUILDING
 REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR
 TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME
 OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
 ****NEED ENERGY CALCULATIONS TO BE PROPERLY SIGNED BY
 THE OWNER AND ALL PLANS NEED THE ENGINEER'S SEAL AND
 SIGNATURE BEFORE APPROVAL.
  
  
  
 ORIGINAL COMMENT:
 1- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 SEC. R401.3 FBC-RESIDENTIAL (DRAINAGE).
 SEC. 107.2.5 CITY AMENDMENTS (SITE PLAN).
 SEC. 110.9 CITY AMENDMENTS (IMPACT OF CONSTRUCTION).
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 2- OK.
  
 3-OK
  
 ORIGINAL COMMENT:
 4- A)DESIGN PRESSURES SHOWN FOR NEW MASTER BEDROOM
 DOUBLE DOORS AND NEW FAMILY ROOM SINGLE DOOR DON'T
 CORRESPOND TO THE EFFECTIVE WIND AREA SHOWN ON
 COMPONENTS AND CLADDING DESIGN PRESSURES ON SHEET 5.1.
 REVISE AS REQUIRED. SEE SIZE OF DOORS AND REVISE AS
 REQUIRED.
  
 RESPONSE:
 PARTIALLY ADDRESSED. THE DOUBLE DOORS ARE CORRECT BUT
 SINGLE DOOR IS NOT. THE LOADS FOR SINGLE DOOR "01" NEED
 TO BE REVISED. NEED TO USE DESIGN PRESSURES FOR THE
 LOWER EFFECTIVE AREA AS REQUIRED BY FOOTNOTE "B" OF
 TABLE R301.2(2)FBC-RESIDENTIAL. SEE TABLE FOR DESIGN
 PRESSURES OF 20S.F. EFFECTIVE WIND AREA AND REVISE AS
 REQUIRED. REMEMBER THAT DESIGN PRESSURES ON THIS TABLE
 NEED TO BE ADJUSTED WITH THE EXPOSURE AND HEIGHT
 COEFFICIENT OF TABLE R301.2(3) FBC-RESIDENTIAL.
  
 ORIGINAL COMMENT:
 B) GARAGE DOORS DESIGN PRESSURES SHOWN ON THE
 COMPONENTS AND CLADDING DESIGN PRESSURES ON SHEET 5.1
 DON'T CORRESPOND TO THE ONES SHOWN ON TABLE 301.2(4)
 FBC-RESIDENTIAL WHEN MULTIPLIED BY THE COEFFICIENT FOR
 EXPOSURE "C". SEE TABLE R301.2(3) FBC-RESIDENTIAL AND
 REVISE AS REQUIRED.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 5- ENERGY CALCULATIONS SUBMITTED:
 ORIGINAL COMMENT:
 A) THE ENERGY FORM R405-2017 IS REQUIRED TO BE
 CERTIFIED AT THE BOTTOM BY THE OWNER OR OWNER'S LEGALLY
 DESIGNATED AGENT AS REQUIRED BY SEC. R103.1.1.2
 FBC-ENERGY CONSERVATION, 6TH EDITION (2017).
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 B)OK.
  
 C) OK.
  
 D) OK.
  
 E) OK.
  
 ORIGINAL COMMENT:
 6- ENGINEER OF RECORD TO SPECIFY ROOF TILE FASTENING IN
 THE CONSTRUCTION DOCUMENTS. SEC. 107.2.1.1 CITY
 AMENDMENTS. IF SPECIFYING ROOF TILE ADHESIVE, THEN
 SPECIFY PADDY SIZE AND PROVIDE PRODUCT APPROVAL. IF
 SPECIFYING SCREWS, THEN SPECIFY SCREW SIZE AND NUMBER
 OF SCREWS.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 7-PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. CONTRACTOR TO ADVICE IF SUBMITTING THIS
 INFORMATION LATER).
  
 ORIGINAL COMMENT:
 A)WINDOW MULLIONS AS SHOWN ON PLANS. AND REQUIRED:
 CLEARLY SPECIFY MULLION SIZE TO BE USED TO VERIFY
 COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 B)FIXED WINDOWS. PROVIDE FLORIDA PRODUCT APPROVAL COVER
 PAGE THAT CORRESPONDS TO DRAWINGS SUBMITTED. COVER PAGE
 SUBMITTED IS FOR MANY DIFFERENT PRODUCT APPROVAL
 NUMBERS. UNABLE TO IDENTIFY THE ONE THAT CORRESPONDS TO
 DRAWING SUBMITTED.
  
 RESPONSE:
 PARTIALLY DONE. PROVIDE COMPLETE INFORMATION. PROVIDE
 FLORIDA PRODUCT APPROVAL COVER PAGE THAT CORRESPONDS TO
 DRAWINGS SUBMITTED. SEC. 107.2.1 CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 C) ROOF TILE ADHESIVE IF SPECIFIED BY THE ENGINEER OF
 RECORD. SEE ROOF TILE NOA SUBMITTED FOR LISTED
 ADHESIVES. AND CLEARLY MARK PADDY SIZE AS REQUIRED BY
 CITY POLICY FOR ALL ROOFING PERMITS.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 D) DOUBLE DOORS AS SHOWN FOR NEW STORAGE.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ABOVE PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1
 CITY AMENDMENTS
  
 9- OK.
  
 10- OK.
  
 NEW COMMENT:
 11- ALL PLANS ON BOTH SETS NEED TO HAVE THE SEAL AND
 SIGNATURE OF THE ENGINEER OF RECORD AS REQUIRED BY
 CHAPTER 471 F.S. WHEN SUBMITTING PLANS/DOCUMENTS FOR
 PUBLIC RECORDS.
  
  
 12- WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
 RESPONSE:
 ORIGINAL PLANS AND SUBMITTALS (ENERGY CALCULATIONS)
 WERE NOT RE-SUBMITTED. IN THE FUTURE PLEASE RES-SUBMIT
 EVERYTHING THAT WAS REVIEWED IN ORDER TO USE THEM FOR
 REFERENCE AND EXPEDITE THE REVIEW PROCESS.
  
 EVEN THOUGH RESPONSE LETTER IS NOT MANDATORY IT IT'S
 VERY HELPFUL TO PROVIDE ONE IN ORDER TO TO EXPEDITE THE
 REVIEW PROCESS.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  