Plan Review Notes For Permit 19030429 |
Permit Number |
19030429 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-03-27 07:01:54 | PLUMBING 1ST REVIEW**DENIED** | | | | 1) PROVIDE WATER HEATER INSTALLATION MANUAL/ SPEC | | SHOWING THE EFFICIENCYRATING OF E.F .97 AS CALLED OUT | | IN THE R405 FORM. FBC 107.2.1. | | | | 2) PROVIDE A SHOWER DETAIL AND PROVIDE WHAT SHOWER PAN | | MATERIAL IS BEING USED. FBC 107.2.1 | | | | 3) PLUMBING ISOMETRIC DRAWING PROVIDE ON SHT. 7.1 HAS | | THE WASHING MACHINE AND LAUNDRY TUB DISCHARGING INTO | | THE BATHROOM GROUP WET VENT. FIXTURES OUTSIDE OF THE | | BATHROOM GROUP ARE NOT PERMITTED TO DISCHARGE INTO THE | | BATHROOM GROUPS HORIZONTAL WET VENT AND SHALL DISCHARGE | | DOWNSTREAM OF THE BATHROM GROUP. FBC-R P3108.1 | | | | | | TIM HUNT | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | CITY OF WEST PALM BEACH | | 561-248-2703 | | THUNT@CGA SOLUTIONS.COM | | | | |
|