2019-04-16 18:26:26 | RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW |
| COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| 1- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE |
| FOLLOWING: |
| SEC. R401.3 FBC-RESIDENTIAL (DRAINAGE). |
| SEC. 107.2.5 CITY AMENDMENTS (SITE PLAN). |
| SEC. 110.9 CITY AMENDMENTS (IMPACT OF CONSTRUCTION). |
| |
| 2- DESIGN PARAMETERS ON SHEET 3.1: |
| A)ENGINEER OF RECORD IS SPECIFYING CONSTRUCTION TYPE |
| IIIB. ACCORDING TO TABLE 601 FBC TYPE III CONSTRUCTION |
| REQUIRES TWO HOURS FIRE RESISTANCE ON ALL EXTERIOR |
| BEARING WALLS. PROVIDE COMPLETE DETAILS AND |
| SPECIFICATIONS SHOWING HOW THE EXTERIOR WALLS PROVIDE 2 |
| HOUR FIRE RATING. AND , PROVIDE MANUFACTURER'S |
| SPECIFICATION FOR TWO HOUR FIRE RATED CONCRETE BLOCK. |
| NOTE: TYPICALLY ONE AND TWO FAMILY STRUCTURES ARE |
| CONSTRUCTION TYPE VB. CLARIFY WHY SPECIFYING |
| CONSTRUCTION TYPE IIIB. |
| |
| B) ROOF LOADS ARE NOT CLEAR. DOES THE TOTAL ROOF LIVE |
| INCLUDE THE TOP AND BOTTOM TRUSS CHORDS?. |
| AND, DOES THE TOTAL ROOF DEAD LOAD INCLUDE THE TOP AND |
| BOTTOM TRUSS CHORDS? ENGINEER OF RECORD TO CLARIFY. |
| CLEARLY SPECIFY THE TOP AND BOTTOM LIVE AND DEAD CHORDS |
| TO AVOID CONFLICTS/DELAYS. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| 3- ENGINEER OF RECORD TO SPECIFY INSULATION ON WALL |
| BETWEEN THE NEW MASTER BEDROOM AND NEW STORAGE AS |
| REQUIRED BY SEC. R103.2 AND R103.2.1 FBC-ENERGY |
| CONSERVATION. |
| |
| 4- A)DESIGN PRESSURES SHOWN FOR NEW MASTER BEDROOM |
| DOUBLE DOORS AND NEW FAMILY ROOM SINGLE DOOR DON'T |
| CORRESPOND TO THE EFFECTIVE WIND AREA SHOWN ON |
| COMPONENTS AND CLADDING DESIGN PRESSURES ON SHEET 5.1. |
| REVISE AS REQUIRED. SEE SIZE OF DOORS AND REVISE AS |
| REQUIRED. |
| |
| B) GARAGE DOORS DESIGN PRESSURES SHOWN ON THE |
| COMPONENTS AND CLADDING DESIGN PRESSURES ON SHEET 5.1 |
| DON'T CORRESPOND TO THE ONES SHOWN ON TABLE 301.2(4) |
| FBC-RESIDENTIAL WHEN MULTIPLIED BY THE COEFFICIENT FOR |
| EXPOSURE "C". SEE TABLE R301.2(3) FBC-RESIDENTIAL AND |
| REVISE AS REQUIRED. |
| |
| 5- ENERGY CALCULATIONS SUBMITTED: |
| A) THE ENERGY FORM R405-2017 IS REQUIRED TO BE |
| CERTIFIED AT THE BOTTOM BY THE OWNER OR OWNER?S LEGALLY |
| DESIGNATED AGENT AS REQUIRED BY SEC. R103.1.1.2 |
| FBC-ENERGY CONSERVATION, 6TH EDITION (2017). |
| |
| B)PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| INCLUDING BUILDER NAME. SEC. R101.5.1.1.2 FBC-ENERGY |
| CONSERVATION. |
| |
| C) WALL TYPES ITEM #9 IS MISSING THE INFORMATION FOR |
| THE WALL BETWEEN THE NEW MASTER BEDROOM AND THE NEW |
| STORAGE. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| D) REVISE ROOF MATERIAL SPECIFIED ON PAGE 2 OF 4 TO |
| MATCH PLANS AND PRODUCT APPROVAL SUBMITTED. THIS IS NOT |
| SHINGLES. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| E) REVISE THE ATTIC VENT RATIO ON PAGE 2 OF 4. THE |
| RATIO IS 1/150 NOT 1/300. SEE SEC. R806.2 |
| FBC-RESIDENTIAL. OR, PERSON PREPARING THE ENERGY |
| CALCULATIONS TO PROVIDE COMPLETE DOCUMENTATION SHOWING |
| COMPLIANCE WITH THE 1/300 RATIO AS REQUIRED BY THE |
| EXCEPTION ON SEC. R806.2. |
| |
| 6- ENGINEER OF RECORD TO SPECIFY ROOF TILE FASTENING IN |
| THE CONSTRUCTION DOCUMENTS. SEC. 107.2.1.1 CITY |
| AMENDMENTS. IF SPECIFYING ROOF TILE ADHESIVE, THEN |
| SPECIFY PADDY SIZE AND PROVIDE PRODUCT APPROVAL. IF |
| SPECIFYING SCREWS, THEN SPECIFY SCREW SIZE AND NUMBER |
| OF SCREWS. |
| |
| 7-PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.001 FOR: |
| A)WINDOW MULLIONS AS SHOWN ON PLANS. AND REQUIRED: |
| CLEARLY SPECIFY MULLION SIZE TO BE USED TO VERIFY |
| COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES. |
| |
| B)FIXED WINDOWS. PROVIDE FLORIDA PRODUCT APPROVAL COVER |
| PAGE THAT CORRESPONDS TO DRAWINGS SUBMITTED. COVER PAGE |
| SUBMITTED IS FOR MANY DIFFERENT PRODUCT APPROVAL |
| NUMBERS. UNABLE TO IDENTIFY THE ONE THAT CORRESPONDS TO |
| DRAWING SUBMITTED. |
| |
| C) ROOF TILE ADHESIVE IF SPECIFIED BY THE ENGINEER OF |
| RECORD. SEE ROOF TILE NOA SUBMITTED FOR LISTED |
| ADHESIVES. AND CLEARLY MARK PADDY SIZE AS REQUIRED BY |
| CITY POLICY FOR ALL ROOFING PERMITS. |
| |
| D) DOUBLE DOORS AS SHOWN FOR NEW STORAGE. |
| |
| 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS |
| |
| 9- PROVIDE SURVEY OR SITE PLAN SHOWING LOCATION OF |
| ADDITION, PROPERTY LINES, SETBACKS AS REQUITED BY SEC. |
| 107.3.5.3 CITY AMENDMENTS. |
| |
| 10- FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS AND |
| SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE |
| STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, INTERIOR |
| FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN |
| FEES, MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING |
| ONLY LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE |
| LATEST PUBLISHED DATA OF NATIONAL CONSTRUCTION COST |
| ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS |
| PUBLISHED BY INTERNATIONAL CODE CONGRESS. VALUATION WAS |
| UPDATED TO $241,657. THE PERMIT FEE BALANCE IS |
| $4339.51. |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND |
| REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. |
| PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD |
| DRAWINGS/DOCUMENTS FOR REFERENCE. |
| |