Plan Review Notes For Permit 19030239 |
Permit Number |
19030239 |
|
Review Stop |
B |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2019-09-13 19:08:13 | FOUNDATION PERMIT APPROVED WITH PROVISO (PROVIDE | | INFORMATION THAT REQUIRES PLAN REVIEW PRIOR TO | | INSPECTIONS TO AVOID CONFLICTS/DELAYS): | | 1- SHEET A-2.1: | | A) REVISE SIZE OF GRATE SHOWN ON THE ENLARGED GRATE | | DETAIL. IT SHOULD BE 4.75' NOT 14.75' AND SPECIFY SIZE | | OF OPENINGS. NOT LESS THAN 3" MIN. SEC. 2.7.2.1 | | ASCE/SEI 24-14. | | 2- PROVIDE COMPLETE/REVISED PROPOSED "CONSTRUCTION | | DRAWINGS" ELEVATION CERTIFICATE. ADDITIONAL ELEVATION | | CERTIFICATES WILL BE REQUIRED FOR BUILDING UNDER | | CONSTRUCTION AND FINISHED CONSTRUCTION. | | NOTE: GARAGE IS CONSIDERED AN ATTACHED GARAGE. | | 3- SURVEYOR'S NOTE #13 SPECIFIES BASE FLOOD ELEVATION | | OF 12.7 FEET. SPECIFY IF N.A.V.D 1988 OR N.G.V.D 1929. | | 4- BASED ON THE HEIGHT OF THE BUILDING, A BARRIER AND | | COVERED WALKWAY FOR PROTECTION OF PEDESTRIANS WILL BE | | REQUIRED. SEC. 3306.1 FBC-BUILDING. | | 5- ART IN PUBLIC PLACES. PLEASE CONTACT MS. SYBILLE | | WELTER ART IN PUBLIC PLACES COORDINATOR 822-1515 | | E-MAIL: [email protected] FOR MORE INFORMATION. | | | | |
|