Plan Review Notes For Permit 19030239 |
Permit Number |
19030239 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2019-06-12 12:18:46 | PLUMBING 2ND REVIEW**DENIED**PLAN REVIEW WAS LIMITED TO | | THE FOUNDATION AND 1ST FLOOR ONLY. A COMPLETE PLAN | | REVIEW WAS NOT PERFORMED. | | | | 1) PROVIDE A 1ST FLOOR SANITARY AND WATER RISER | | DRAWING. FBC 107.3.5 | | | | 2) FILE 087, 088, AND 089 SEEM TO BE CORRUPTED AND | | UNABLE TO OPEN. PLEASE RESUBMIT. FBC 107.3.5 | | | | 3) PROVIDE 1ST FLOOR PLAN SHOWING ALL FAIR HOUSING | | (FHA) REQUIRED ELEMENTS IN EACH UNIT( CLEAR FLOOR | | SPACE, TURNING SPACE) AND LIST WHAT DESIGN SPEC EACH | | UNIT WILL BE. FBC 107.3.5 | | | | 4) PROVIDE 1ST FLOOR PLAN SHOWING ACCESSIBILITY | | REQUIREMENTS ARE BEING MEET IN THE PUBLIC RESTROOMS. | | CLEAR FLOOR SPACE, TURNING RADIUS, AND ACCESSIBLE | | ROUTES. FBC 107.3.5 | | | | 5) PROVIDE STORM WATER RISER ISOMETRIC IF ANY. FBC | | 107.3.5 | | | | *****PLAN REVIEW WAS LIMITED TO THE FOUNDATION AND 1ST | | FLOOR ONLY. A COMPLETE PLAN REVIEW WAS NOT | | PERFORMED***** | | | | TIM HUNT | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | CITY OF WEST PALM BEACH | | 561-248-2703 | | [email protected] | | [email protected] | | |
|