Plan Review Notes
Plan Review Notes For Permit 19030239
Permit Number 19030239
Review Stop P
Sequence Number 2
Notes
Date Text
2019-06-12 12:18:46PLUMBING 2ND REVIEW**DENIED**PLAN REVIEW WAS LIMITED TO
 THE FOUNDATION AND 1ST FLOOR ONLY. A COMPLETE PLAN
 REVIEW WAS NOT PERFORMED.
  
 1) PROVIDE A 1ST FLOOR SANITARY AND WATER RISER
 DRAWING. FBC 107.3.5
  
 2) FILE 087, 088, AND 089 SEEM TO BE CORRUPTED AND
 UNABLE TO OPEN. PLEASE RESUBMIT. FBC 107.3.5
  
 3) PROVIDE 1ST FLOOR PLAN SHOWING ALL FAIR HOUSING
 (FHA) REQUIRED ELEMENTS IN EACH UNIT( CLEAR FLOOR
 SPACE, TURNING SPACE) AND LIST WHAT DESIGN SPEC EACH
 UNIT WILL BE. FBC 107.3.5
  
 4) PROVIDE 1ST FLOOR PLAN SHOWING ACCESSIBILITY
 REQUIREMENTS ARE BEING MEET IN THE PUBLIC RESTROOMS.
 CLEAR FLOOR SPACE, TURNING RADIUS, AND ACCESSIBLE
 ROUTES. FBC 107.3.5
  
 5) PROVIDE STORM WATER RISER ISOMETRIC IF ANY. FBC
 107.3.5
  
 *****PLAN REVIEW WAS LIMITED TO THE FOUNDATION AND 1ST
 FLOOR ONLY. A COMPLETE PLAN REVIEW WAS NOT
 PERFORMED*****
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]
  