Plan Review Notes
Plan Review Notes For Permit 19030239
Permit Number 19030239
Review Stop THRESHOLD
Sequence Number 1
Notes
Date Text
2019-07-10 13:37:4807/31/19 REVISED COMMENTS:
  
 1- PLEASE NOTE A 7 STORY BUILDING QUALIFIES AS A
 THRESHOLD BUILDING / FL S. S. 553.71(7) THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DEFINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 A) THRESHOLD INSPECTOR: CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED TO BE
 FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED AND
 RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED
 BEFORE PERMIT ISSUANCE WILL TAKE PLACE.
  
 RESPONSE:
 (1)THE THRESHOLD INSPECTION FORM SUBMITTED IS OLD. NEED
 TO USE REVISED FORM. ALSO, THE FORM NEEDS TO BE SIGNED
 AND SEALED BY THE ENGINEER AS REQUIRED BY CHAPTER 471
 AND CITY THRESHOLD BUILDINGS SPECIAL INSPECTOR PROGRAM.
 SEE REVISED CITY THRESHOLD BUILDINGS SPECIAL INSPECTOR
 PROGRAM DATED OCTOBER 2018 AND USE PROPER FORMS.
  
 (2)THRESHOLD INSPECTOR QUALIFICATIONS ARE REQUIRED TO
 BE REVIEWED/ACCEPTED BY THE ENGINEER OF RECORD WHO
 PREPARED THE THRESHOLD INSPECTION PLAN. SEE SECTION B
 OF PART I OF THRESHOLD INSPECTION PLAN ON SHEET S-1.1.
 SEC. 110.8.1 CITY AMENDMENTS.
  
 B) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 MINIMUM BUILDING CODES AND THE APPLICABLE FIRE-SAFETY
 STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTES.
  
 RESPONSE:
 ONLY THE ARCHITECTURAL PLANS HAVE THIS STATEMENT. THE
 STRUCTURAL PLANS DON'T HAVE THIS STATEMENT.
  
 C) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA. FOR A JOBSITE
 REPRESENTATIVE IS NOT AN ARCHITECT OR ENGINEER THEN
 THEY MUST HAVE A BN LICENSE NUMBER UNDER
 F. S. 468.
  
 RESPONSE:
 MISSING THE RESUME FOR ONE OF THE THRESHOLD INSPECTOR'S
 REPRESENTATIVE. PROVIDE THE RESUME FOR CHARLES MOCK.
  
 D) PLEASE CALL THE CITY OF WEST PALM BEACH'S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  