Plan Review Notes
Plan Review Notes For Permit 19030239
Permit Number 19030239
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-03-22 11:30:08THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET 7 - THERE IS AN INDICATION OF AN 8" D.I.P FIRE
 LINE WITH A COMMENT "INSTALLED BY A LICENSED FIRE
 SPRINKLER CONTRACTOR".
  
 ALL FIRE LINE UNDERGROUND SHALL BE DONE BY STATE OF
 FLORIDA LICENSED FIRE PROTECTION CONTRACTOR.
  
 PER FS 633.102
 (1)??BOARD? MEANS THE FLORIDA FIRE SAFETY BOARD.
 (2)??CONTRACTING? MEANS ENGAGING IN BUSINESS AS A
 CONTRACTOR.
 (3)(A)?CONTRACTOR I? MEANS A CONTRACTOR WHOSE BUSINESS
 INCLUDES THE EXECUTION OF CONTRACTS REQUIRING THE
 ABILITY TO LAY OUT, FABRICATE, INSTALL, INSPECT, ALTER,
 REPAIR, AND SERVICE ALL TYPES OF FIRE PROTECTION
 SYSTEMS, EXCLUDING PRE-ENGINEERED SYSTEMS.
 (B)??CONTRACTOR II? MEANS A CONTRACTOR WHOSE BUSINESS
 IS LIMITED TO THE EXECUTION OF CONTRACTS REQUIRING THE
 ABILITY TO LAY OUT, FABRICATE, INSTALL, INSPECT, ALTER,
 REPAIR, AND SERVICE WATER SPRINKLER SYSTEMS, WATER
 SPRAY SYSTEMS, FOAM-WATER SPRINKLER SYSTEMS, FOAM-WATER
 SPRAY SYSTEMS, STANDPIPES, COMBINATION STANDPIPES AND
 SPRINKLER RISERS, ALL PIPING THAT IS AN INTEGRAL PART
 OF THE SYSTEM BEGINNING AT THE POINT OF SERVICE AS
 DEFINED IN THIS SECTION, SPRINKLER TANK HEATERS, AIR
 LINES, THERMAL SYSTEMS USED IN CONNECTION WITH
 SPRINKLERS, AND TANKS AND PUMPS CONNECTED THERETO,
 EXCLUDING PRE-ENGINEERED SYSTEMS.
 (C)??CONTRACTOR III? MEANS A CONTRACTOR WHOSE BUSINESS
 IS LIMITED TO THE EXECUTION OF CONTRACTS REQUIRING THE
 ABILITY TO FABRICATE, INSTALL, INSPECT, ALTER, REPAIR,
 AND SERVICE CARBON DIOXIDE SYSTEMS, FOAM EXTINGUISHING
 SYSTEMS, DRY CHEMICAL SYSTEMS, AND HALON AND OTHER
 CHEMICAL SYSTEMS, EXCLUDING PRE-ENGINEERED SYSTEMS.
 (D)??CONTRACTOR IV? MEANS A CONTRACTOR WHOSE BUSINESS
 IS LIMITED TO THE EXECUTION OF CONTRACTS REQUIRING THE
 ABILITY TO LAY OUT, FABRICATE, INSTALL, INSPECT, ALTER,
 REPAIR, AND SERVICE AUTOMATIC FIRE SPRINKLER SYSTEMS
 FOR DETACHED ONE-FAMILY DWELLINGS, DETACHED TWO-FAMILY
 DWELLINGS, AND MOBILE HOMES, EXCLUDING PRE-ENGINEERED
 SYSTEMS AND EXCLUDING SINGLE-FAMILY HOMES IN CLUSTER
 UNITS, SUCH AS APARTMENTS, CONDOMINIUMS, AND ASSISTED
 LIVING FACILITIES OR ANY BUILDING THAT IS CONNECTED TO
 OTHER DWELLINGS. A CONTRACTOR IV IS LIMITED TO THE
 SCOPE OF PRACTICE SPECIFIED IN NFPA 13D.
 (E)??CONTRACTOR V? MEANS A CONTRACTOR WHOSE BUSINESS IS
 LIMITED TO THE EXECUTION OF CONTRACTS REQUIRING THE
 ABILITY TO FABRICATE, INSTALL, INSPECT, ALTER, REPAIR,
 AND SERVICE THE UNDERGROUND PIPING FOR A FIRE
 PROTECTION SYSTEM USING WATER AS THE EXTINGUISHING
 AGENT BEGINNING AT THE POINT OF SERVICE AS DEFINED IN
 THIS ACT AND ENDING NO MORE THAN 1 FOOT ABOVE THE
 FINISHED FLOOR.
  
 PLEASE REVIEW AND CORRECT AND ENSURE COMPLIANCE.
  
  
  
 2) SHEET 7 - THERE IS AN INDICATION OF AN 8" D.D.C.V. -
 IS THIS DDCV A FIRE LINE DDCV?
  
 ALL FIRE LINE UNDERGROUND SHALL COMPLY WITH NFPA 24 AND
 IF THIS IS A FIRE LINE DDCV IT IS WITHIN THE FOOTPRINT
 OF THE BUILDING AND IS NOT IN COMPLIANCE WITH THE CODE.
  
 PER NFPA 24
  
 6.2.11 ALL CONNECTIONS TO PRIVATE FIRE SERVICE MAINS
 FOR FIRE
 PROTECTION SYSTEMS SHALL BE ARRANGED IN ACCORDANCE WITH
 ONE
 OF THE FOLLOWING SO THAT THEY CAN BE ISOLATED:
 (1)*A POST INDICATOR VALVE INSTALLED NOT LESS THAN 40
 FT (12 M)
 FROM THE BUILDING
 (A) FOR BUILDINGS LESS THAN 40 FT (12 M) IN HEIGHT, A
 POST
 INDICATOR VALVE SHALL BE PERMITTED TO BE INSTALLED
 CLOSER THAN 40 FT (12 M) BUT AT LEAST AS FAR FROM THE
 BUILDING AS THE HEIGHT OF THE WALL FACING THE POST
 INDICATOR
 VALVE.
 (2) A WALL POST INDICATOR VALVE
 (3) AN INDICATING VALVE IN A PIT, INSTALLED IN
 ACCORDANCE WITH
 SECTION 6.4
 (4)*A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING
 VALVE NOT
 LESS THAN 40 FT (12 M) FROM THE BUILDING
 (A) FOR BUILDINGS LESS THAN 40 FT (12 M) IN HEIGHT, A
 BACKFLOW
 PREVENTER WITH AT LEAST ONE INDICATING VALVE SHALL
 BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FT (12 M)
 BUT AT LEAST AS FAR FROM THE BUILDING AS THE HEIGHT OF
 THE WALL FACING THE BACKFLOW PREVENTER.
  
 6.5 BACKFLOW PREVENTION ASSEMBLIES.
 6.5.1 WHERE USED IN ACCORDANCE WITH 6.2.11(4), BACKFLOW
 PREVENTION
 ASSEMBLIES SHALL BE INSTALLED IN ACCORDANCE WITH THEIR
 INSTALLATION INSTRUCTIONS.
 6.5.2 WHERE BACKFLOW PREVENTION ASSEMBLIES ARE USED,
 THEY
 SHALL BE PROTECTED AGAINST MECHANICAL DAMAGE WHERE
 NEEDED.
  
 PLEASE REVIEW AND CORRECT THE LOCATION PER THE
 REQUIREMENT.
  
  
 3) THERE ARE NO INDICATIONS OF A FIRE PUMP ROOM AND IF
 THAT FIRE PUMP ROOM HAS A FLOOR DRAIN AS REQUIRED.
  
 PER NFPA 20
  
 4.12.7* DRAINAGE.
 4.12.7.1 FLOORS SHALL BE PITCHED FOR ADEQUATE DRAINAGE
 OF ESCAPING
 WATER AWAY FROM CRITICAL EQUIPMENT SUCH AS THE PUMP,
 DRIVER, CONTROLLER, AND SO FORTH.
 4.12.7.2 THE PUMP ROOM OR PUMP HOUSE SHALL BE PROVIDED
 WITH A FLOOR DRAIN THAT WILL DISCHARGE TO A FROST-FREE
 LOCATION.
  
 PLEASE REVIEW AND CORRECT OR CONFIRM AND PROVIDE A NOTE
 THAT IT SHALL BE INSTALLED WITH THE FOUNDATION.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
2019-03-20 13:30:07PLANS ARE STAMPED I JUST PLACED RESULTS INTO THE SYSTEM
 JLEAHY