2019-03-22 11:30:08 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) SHEET 7 - THERE IS AN INDICATION OF AN 8" D.I.P FIRE |
| LINE WITH A COMMENT "INSTALLED BY A LICENSED FIRE |
| SPRINKLER CONTRACTOR". |
| |
| ALL FIRE LINE UNDERGROUND SHALL BE DONE BY STATE OF |
| FLORIDA LICENSED FIRE PROTECTION CONTRACTOR. |
| |
| PER FS 633.102 |
| (1)??BOARD? MEANS THE FLORIDA FIRE SAFETY BOARD. |
| (2)??CONTRACTING? MEANS ENGAGING IN BUSINESS AS A |
| CONTRACTOR. |
| (3)(A)?CONTRACTOR I? MEANS A CONTRACTOR WHOSE BUSINESS |
| INCLUDES THE EXECUTION OF CONTRACTS REQUIRING THE |
| ABILITY TO LAY OUT, FABRICATE, INSTALL, INSPECT, ALTER, |
| REPAIR, AND SERVICE ALL TYPES OF FIRE PROTECTION |
| SYSTEMS, EXCLUDING PRE-ENGINEERED SYSTEMS. |
| (B)??CONTRACTOR II? MEANS A CONTRACTOR WHOSE BUSINESS |
| IS LIMITED TO THE EXECUTION OF CONTRACTS REQUIRING THE |
| ABILITY TO LAY OUT, FABRICATE, INSTALL, INSPECT, ALTER, |
| REPAIR, AND SERVICE WATER SPRINKLER SYSTEMS, WATER |
| SPRAY SYSTEMS, FOAM-WATER SPRINKLER SYSTEMS, FOAM-WATER |
| SPRAY SYSTEMS, STANDPIPES, COMBINATION STANDPIPES AND |
| SPRINKLER RISERS, ALL PIPING THAT IS AN INTEGRAL PART |
| OF THE SYSTEM BEGINNING AT THE POINT OF SERVICE AS |
| DEFINED IN THIS SECTION, SPRINKLER TANK HEATERS, AIR |
| LINES, THERMAL SYSTEMS USED IN CONNECTION WITH |
| SPRINKLERS, AND TANKS AND PUMPS CONNECTED THERETO, |
| EXCLUDING PRE-ENGINEERED SYSTEMS. |
| (C)??CONTRACTOR III? MEANS A CONTRACTOR WHOSE BUSINESS |
| IS LIMITED TO THE EXECUTION OF CONTRACTS REQUIRING THE |
| ABILITY TO FABRICATE, INSTALL, INSPECT, ALTER, REPAIR, |
| AND SERVICE CARBON DIOXIDE SYSTEMS, FOAM EXTINGUISHING |
| SYSTEMS, DRY CHEMICAL SYSTEMS, AND HALON AND OTHER |
| CHEMICAL SYSTEMS, EXCLUDING PRE-ENGINEERED SYSTEMS. |
| (D)??CONTRACTOR IV? MEANS A CONTRACTOR WHOSE BUSINESS |
| IS LIMITED TO THE EXECUTION OF CONTRACTS REQUIRING THE |
| ABILITY TO LAY OUT, FABRICATE, INSTALL, INSPECT, ALTER, |
| REPAIR, AND SERVICE AUTOMATIC FIRE SPRINKLER SYSTEMS |
| FOR DETACHED ONE-FAMILY DWELLINGS, DETACHED TWO-FAMILY |
| DWELLINGS, AND MOBILE HOMES, EXCLUDING PRE-ENGINEERED |
| SYSTEMS AND EXCLUDING SINGLE-FAMILY HOMES IN CLUSTER |
| UNITS, SUCH AS APARTMENTS, CONDOMINIUMS, AND ASSISTED |
| LIVING FACILITIES OR ANY BUILDING THAT IS CONNECTED TO |
| OTHER DWELLINGS. A CONTRACTOR IV IS LIMITED TO THE |
| SCOPE OF PRACTICE SPECIFIED IN NFPA 13D. |
| (E)??CONTRACTOR V? MEANS A CONTRACTOR WHOSE BUSINESS IS |
| LIMITED TO THE EXECUTION OF CONTRACTS REQUIRING THE |
| ABILITY TO FABRICATE, INSTALL, INSPECT, ALTER, REPAIR, |
| AND SERVICE THE UNDERGROUND PIPING FOR A FIRE |
| PROTECTION SYSTEM USING WATER AS THE EXTINGUISHING |
| AGENT BEGINNING AT THE POINT OF SERVICE AS DEFINED IN |
| THIS ACT AND ENDING NO MORE THAN 1 FOOT ABOVE THE |
| FINISHED FLOOR. |
| |
| PLEASE REVIEW AND CORRECT AND ENSURE COMPLIANCE. |
| |
| |
| |
| 2) SHEET 7 - THERE IS AN INDICATION OF AN 8" D.D.C.V. - |
| IS THIS DDCV A FIRE LINE DDCV? |
| |
| ALL FIRE LINE UNDERGROUND SHALL COMPLY WITH NFPA 24 AND |
| IF THIS IS A FIRE LINE DDCV IT IS WITHIN THE FOOTPRINT |
| OF THE BUILDING AND IS NOT IN COMPLIANCE WITH THE CODE. |
| |
| PER NFPA 24 |
| |
| 6.2.11 ALL CONNECTIONS TO PRIVATE FIRE SERVICE MAINS |
| FOR FIRE |
| PROTECTION SYSTEMS SHALL BE ARRANGED IN ACCORDANCE WITH |
| ONE |
| OF THE FOLLOWING SO THAT THEY CAN BE ISOLATED: |
| (1)*A POST INDICATOR VALVE INSTALLED NOT LESS THAN 40 |
| FT (12 M) |
| FROM THE BUILDING |
| (A) FOR BUILDINGS LESS THAN 40 FT (12 M) IN HEIGHT, A |
| POST |
| INDICATOR VALVE SHALL BE PERMITTED TO BE INSTALLED |
| CLOSER THAN 40 FT (12 M) BUT AT LEAST AS FAR FROM THE |
| BUILDING AS THE HEIGHT OF THE WALL FACING THE POST |
| INDICATOR |
| VALVE. |
| (2) A WALL POST INDICATOR VALVE |
| (3) AN INDICATING VALVE IN A PIT, INSTALLED IN |
| ACCORDANCE WITH |
| SECTION 6.4 |
| (4)*A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING |
| VALVE NOT |
| LESS THAN 40 FT (12 M) FROM THE BUILDING |
| (A) FOR BUILDINGS LESS THAN 40 FT (12 M) IN HEIGHT, A |
| BACKFLOW |
| PREVENTER WITH AT LEAST ONE INDICATING VALVE SHALL |
| BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FT (12 M) |
| BUT AT LEAST AS FAR FROM THE BUILDING AS THE HEIGHT OF |
| THE WALL FACING THE BACKFLOW PREVENTER. |
| |
| 6.5 BACKFLOW PREVENTION ASSEMBLIES. |
| 6.5.1 WHERE USED IN ACCORDANCE WITH 6.2.11(4), BACKFLOW |
| PREVENTION |
| ASSEMBLIES SHALL BE INSTALLED IN ACCORDANCE WITH THEIR |
| INSTALLATION INSTRUCTIONS. |
| 6.5.2 WHERE BACKFLOW PREVENTION ASSEMBLIES ARE USED, |
| THEY |
| SHALL BE PROTECTED AGAINST MECHANICAL DAMAGE WHERE |
| NEEDED. |
| |
| PLEASE REVIEW AND CORRECT THE LOCATION PER THE |
| REQUIREMENT. |
| |
| |
| 3) THERE ARE NO INDICATIONS OF A FIRE PUMP ROOM AND IF |
| THAT FIRE PUMP ROOM HAS A FLOOR DRAIN AS REQUIRED. |
| |
| PER NFPA 20 |
| |
| 4.12.7* DRAINAGE. |
| 4.12.7.1 FLOORS SHALL BE PITCHED FOR ADEQUATE DRAINAGE |
| OF ESCAPING |
| WATER AWAY FROM CRITICAL EQUIPMENT SUCH AS THE PUMP, |
| DRIVER, CONTROLLER, AND SO FORTH. |
| 4.12.7.2 THE PUMP ROOM OR PUMP HOUSE SHALL BE PROVIDED |
| WITH A FLOOR DRAIN THAT WILL DISCHARGE TO A FROST-FREE |
| LOCATION. |
| |
| PLEASE REVIEW AND CORRECT OR CONFIRM AND PROVIDE A NOTE |
| THAT IT SHALL BE INSTALLED WITH THE FOUNDATION. |
| |
| |
| |
| 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |
| 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |
| |
2019-03-20 13:30:07 | PLANS ARE STAMPED I JUST PLACED RESULTS INTO THE SYSTEM |
| JLEAHY |