2019-04-02 13:36:01 | 1. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, |
| SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN |
| KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, |
| PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS, |
| RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND |
| SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. PROVIDE |
| CORRECTION. NEC 210.12; FBC RE E3902.16 |
| 2. ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND |
| SIGNED/SEALED BY A DESIGN PROFESSIONAL OR THE |
| ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS |
| 471.003(2)(H); 471.025; WPB FBC 107.1 |
| 3. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED |
| PER CODE. PROVIDE FULL FLOOR PLAN SHOWING ALL EXISTING |
| ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS |
| NEW INSTALLATIONS. FBC RE R314.3, R315.1; WPB FBC |
| 107.2.1 |
| 4. THE WALL SPACING REQUIREMENTS FOR KITCHEN COUNTER |
| SPACE STATE THAT RECEPTACLE OUTLETS SHALL BE INSTALLED |
| SO THAT NO POINT ALONG THE WALL LINE IS MORE THAN 24 |
| INCHES MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET |
| IN THAT SPACE. THE PLAN PROVIDED DOES NOT MEET THIS |
| CODE IN SOME AREAS. PROVIDE CORRECTION. NEC |
| 210.52(C)(1); FBC RE E3901.4 |
| 5.A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP |
| CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN. |
| PROVIDE CORRECTION. NEC 210.11(C)(3), 210.52(D); FBC RE |
| E3703.4, E3901.6 |
| 6. 110.26 PROVIDE WORKING CLEARANCE IN FRONT OF PANEL. |
| |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD |
| SHEETS?. |
| |