2019-03-21 15:38:37 | BUILDING PLAN REVIEW |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| |
| JOSEAN A. DUPREY E.I., BN, PX |
| BUILDING PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6716 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 2NDT REVIEW |
| RESULTS: DENIED |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| SAME REPORTS WERE SUBMITTED |
| |
| 1. PLEASE NOTE THAT TEST REPORTS SUBMITTED DO NOT MEET |
| THE TEST PARAMETERS. SEE TEST REPORT ASTM 84-15A PAGE 2 |
| OF 6, THE PRODUCT WAS TESTED UP SIDE DOWN PER CLIENT |
| REQUEST. THEY DID NOT FOLLOWED THE ASTM PROCEDURE. |
| PLEASE SUBMITT TEST DATA FOR A DIFFERENT PRODUCT. |
| |
| TEST REPORTS ARE REQUIRED - MANUFACTURER SPEC SHEETS |
| ARE NOT ACCEPTABLE DUE TO DISCREPANCIES BETWEEN SPEC |
| SHEETS/BROCHURES AND TEST REPORTS FOR SOME |
| MANUFACTURERS (NOT NECESSARILY THE MANUFACTURER |
| SELECTED; THIS IS A GENERAL COMMENT) |
| |
| A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. |
| THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM |
| CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| |
| B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED |
| GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| |
| C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| OR UL 723. |
| |