2019-03-21 15:38:37BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 JOSEAN A. DUPREY E.I., BN, PX
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6716
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2NDT REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 SAME REPORTS WERE SUBMITTED
  
 1. PLEASE NOTE THAT TEST REPORTS SUBMITTED DO NOT MEET
 THE TEST PARAMETERS. SEE TEST REPORT ASTM 84-15A PAGE 2
 OF 6, THE PRODUCT WAS TESTED UP SIDE DOWN PER CLIENT
 REQUEST. THEY DID NOT FOLLOWED THE ASTM PROCEDURE.
 PLEASE SUBMITT TEST DATA FOR A DIFFERENT PRODUCT.
  
 TEST REPORTS ARE REQUIRED - MANUFACTURER SPEC SHEETS
 ARE NOT ACCEPTABLE DUE TO DISCREPANCIES BETWEEN SPEC
 SHEETS/BROCHURES AND TEST REPORTS FOR SOME
 MANUFACTURERS (NOT NECESSARILY THE MANUFACTURER
 SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  