2019-03-12 08:36:41 | PLUMBING 1ST REVIEW**DENIED** | | | | BUILDINGS CONSTRUCTED AFTER MARCH 13, 1991 MUST COMPLY | | WITH FAIR HOUSING ACT (FHA). THIS BUILDING WAS | | CONSTRUCTED IN 2001. YOU MAY WANT TO CONSULT A DESIGN | | PROFESSIOAL WHO IS FAMILIAR WITH THE REQUIREMENTS OF | | FAIR HOUSING. | | | | 1) PROVIDE FLOOR PLAN SHOWING WHAT FHA DESIGN | | SPECIFICATION EACH BATHROOM IS. FBC 107.2.1 | | | | 2) YOU SCOPE OF WORK DRAWING IS BACKWARDS AND DOES NOT | | MATCH THE EXISTING FLOOR PLAN ORIENTATION. FBC 107.1 | | | | 3) PROVIDE DETAIL MEARSUREMENTS SHOWING NEW DOUBLE | | SINKS WILL COMPLY WITH FHA 7.48 AND MAX CABINET HEIGHT | | WILL BE 34" FHA 7.52 | | | | 4) PROVIDE PLAN SHOWING ALL REQUIRED CLEAR FLOR SPACES | | AND APPROCH AS REQUIRED IN FHA CHAPTER 7B | | | | 5) YOUR PLAN SHOW THE SHOWER @ 42" WHICH IS 6" WIDER | | THEN THE EXISTING TUB. TOILETS ARE REQUIRED TO BE A | | 18"MIN FROM THE GRAB BAR SIDE AND 15" ON THE SINK SIDE | | OVERALL MIN 33". FHA 7.43 | | | | 6) SHOWERS ARE NOT PERMITTED TO BE ADJACENT TO A TOILET | | IN A FHA BATHROOM. FHA 7.44 | | | | | | TIM HUNT | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | 561-248-2703 | | | | SAMANTHA HILL | | CHIEF PLAN EXAMINER | | 561-805-6724 |
|