Plan Review Notes For Permit 19030078 |
Permit Number |
19030078 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-03-06 10:17:45 | PERMIT #19030078 | | FIRE REVIEW COMMENTS: | | | | 1) THE OCCUPANT LOAD FOR THE COMBINED 1600 SQ FT OF | | TENTING (4 - 20'X20' TENTS) SHALL COMPLY WITH THE | | OCCUPANT LOAD FACTOR AS LISTED UNDER NFPA 101: CHAPTER | | 7, TABLE 7.3.1.2. MORE SPECIFICALLY, ASSEMBLY USE: LESS | | CONCENTRATED USE, WITHOUT FIXED SEATING - 15 SQ | | FT/PERSON. | | | | 2) PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS | | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE | | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL | | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. | | PROVIDE TYPE K EXTINGUISHERS WHEN COOKING WITH GREASE | | OR WHEN PRODUCING SMOKE OR GREASE-LADEN VAPORS. | | | | 3) TENTS SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM | | BUILDING STRUCTURES. | | | | 4) TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL TYPE, | | OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS | | ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET. | | | | 5) POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS | | LOCATIONS. | | | | 6) IF APPLICABLE, GENERATORS AND OTHER INTERNAL | | COMBUSTION POWER SOURCES SHALL BE SEPARATED FROM TENTS | | BY A MINIMUM OF 5 FEET AND SHALL BE PROTECTED FROM | | CONTACT BY FENCING OR ENCLOSURE. | | | | SUE ELLEN CALDERON | | ASST. FIRE MARSHAL | | [email protected] | | | | |
|