 FIRE REVIEW COMMENTS:
  
 1) THE OCCUPANT LOAD FOR THE COMBINED 1600 SQ FT OF
 TENTING (4 - 20'X20' TENTS) SHALL COMPLY WITH THE
 OCCUPANT LOAD FACTOR AS LISTED UNDER NFPA 101: CHAPTER
 7, TABLE 7.3.1.2. MORE SPECIFICALLY, ASSEMBLY USE: LESS
 CONCENTRATED USE, WITHOUT FIXED SEATING - 15 SQ
 FT/PERSON.
  
 2) PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
 PROVIDE TYPE K EXTINGUISHERS WHEN COOKING WITH GREASE
 OR WHEN PRODUCING SMOKE OR GREASE-LADEN VAPORS.
  
 3) TENTS SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM
 BUILDING STRUCTURES.
  
 4) TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL TYPE,
 OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS
 ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET.
  
 5) POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS
 LOCATIONS.
  
 6) IF APPLICABLE, GENERATORS AND OTHER INTERNAL
 COMBUSTION POWER SOURCES SHALL BE SEPARATED FROM TENTS
 BY A MINIMUM OF 5 FEET AND SHALL BE PROTECTED FROM
 CONTACT BY FENCING OR ENCLOSURE.
  