2019-02-27 12:39:11 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. CLARIFY ON PLAN IF THE SERVICE IS OVERHEAD OR |
| UNDERGROUND, AND REMOVE THE CONFLICTING INFORMATION. |
| NEC 215.5; WPB FBC 107.2.1 |
| 2. PROPER WIRE SIZE FOR A 150 AMP SERVICE IS EITHER #1 |
| COPPER, OR 2/0 ALUMINUM. SPECIFY ON PLAN WHAT SIZE |
| CONDUCTORS ARE BEING USED. THEY SHOULD EITHER BE ALL OF |
| THE SAME SIZE, OR THE 2 UNGROUNDED CONDUCTORS SIZED AS |
| MENTIONED ABOVE AND A REDUCED NEUTRAL IS PERMITTED. NEC |
| 310.15(B)(7) |
| 3. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3 |
| 4. A DISCONNECT IS REQUIRED ON THE EXTERIOR OF THE |
| HOUSE IF THE PANEL WITH MAIN BREAKER IS NOT BACK TO |
| BACK WITH THE METER CAN. CLARIFY ON PLAN WHERE THE |
| PANEL IS IN RELATION TO THE METER, OR PROVIDE A |
| DISCONNECT ADJACENT TO THE METER. NEC 230.70 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| SHEETS. |
| |