2019-03-04 11:26:28 | PERMIT # 19021325 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| FAIL COMMENTS: |
| |
| 1) PER NFPA 101, CHAPTERS 36 & 37 - NEW AND |
| EXISTINGMERCANTILE OCCUPANCY - |
| IN MERCANTILE OCCUPANCIES CLASSIFIED AS ORDINARY |
| HAZARD, TRAVEL DISTANCE SHALL NOT EXCEED 150 FT. |
| IN MERCANTILE OCCUPANCIES CLASSIFIED AS ORDINARY HAZARD |
| IN BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED, |
| SUPERVISED |
| AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH |
| 9.7.1.1(1), TRAVEL DISTANCE SHALL NOT EXCEED 250 FT. |
| |
| 2) SHEET G1.01 INDICATES THE BUILDING IS "UNPROTECTED" |
| WITH A FIRE ALARM. THEREFORE THE TRAVEL DISTANCE OF |
| 186' INDICATED ON SHEET L1.01 EXCEEDS THE PERMITTED |
| TRAVEL DISTANCE AS OUTLINED IN NFPA 101. (SEE ABOVE.) |
| |
| 3) PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION |
| SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND |
| RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION |
| SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A |
| 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A |
| FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED |
| BY EMAIL ([email protected]) OR IN WRITING (FAX: |
| 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE |
| MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.? |
| |
| 4) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE |
| INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER |
| SYSTEM AND/OR FIRE ALARM SYSTEM. |
| |
| |