2019-03-06 16:52:41 | ****CORRECTIONS**** |
| W.P.B. PERMIT: 19021325 |
| REVIEWED: MARCH 6, 2019 |
| |
| DYLAN BATTLES |
| BUILDING PLANS EXAMINER PX4191 |
| [email protected] |
| 561-805-6718 |
| |
| FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| FBC[B] = FBC BUILDING |
| FBC[EXISTING] = FBC EXISTING BUILDING |
| FBC[A] = FBC ACCESSIBILITY |
| FBC[E] = FBC ENERGY CONSERVATION |
| FBC[R] = FBC RESIDENTIAL |
| |
| 1) 301.1 FBC[EXISTING] GENERAL. THE REPAIR, ALTERATION, |
| CHANGE OF OCCUPANCY, ADDITION OR RELOCATION OF ALL |
| EXISTING BUILDINGS SHALL COMPLY WITH ONE OF THE METHODS |
| LISTED IN SECTIONS 301.1.1 THROUGH 301.1.3 AS SELECTED |
| BY THE APPLICANT. SECTIONS 301.1.1 THROUGH 301.1.3 |
| SHALL NOT BE APPLIED IN COMBINATION WITH EACH OTHER. |
| WHICH METHOD IS BEING USED FOR COMPLIANCE? |
| (PRESCRIPTIVE,WORK AREA OR PERFORMANCE) |
| |
| 2) 501 FBC[EXISTING] STATE THE LEVEL OF ALTERATION FOR |
| WORK BEING PERFORMED. |
| THE PLANS STATE LEVEL 1, BUT THIS WOULD BE A LEVEL 2 |
| DUE TO THE RE-ARRANGEMENT OF SPACES AND POSSIBLE A |
| LEVEL 3 IF OVER 50 % OF THE BUILDING IS INCLUDED IN THE |
| WORK. PLEASE REVIEW AND REVISE TO MEET DEFINITION THAT |
| APPLIES. |
| |
| 3) 1004.1 FBC[B] DESIGN OCCUPANT LOAD. IN DETERMINING |
| MEANS OF EGRESS REQUIREMENTS, THE NUMBER OF OCCUPANTS |
| FOR WHOM MEANS OF EGRESS FACILITIES ARE PROVIDED SHALL |
| BE DETERMINED IN ACCORDANCE WITH THIS SECTION. |
| ADD OCCUPANT LOAD ON SHEET L1.01 |
| |
| 4) 302 FBC[B] WHAT IS THE EXISTING OCCUPANCY AND WHAT |
| IS THE PROPOSED OCCUPANCY? |
| PLEASE ADD TO SHEET L1.01 |
| |
| 5) 402.1 FBC[A] PROVIDE ACCESSIBLE ROUTE FROM PARKING |
| LOT. IN ADDITION TO ACCESSIBLE ENTRANCES REQUIRED BY |
| SECTIONS 1105.1.1 THROUGH 1105.1.7 (PARKING GARAGE |
| ENTRANCES, ENTRANCES FROM TUNNELS OR ELEVATED WALKWAYS, |
| RESTRICTED ENTRANCES, ENTRANCES FOR INMATES OR |
| DETAINEES, SERVICE ENTRANCES AND ENTRANCES TO TENANT |
| SPACES, DWELLING UNITS AND SLEEPING UNITS), AT LEAST 60 |
| PERCENT OF ALL PUBLIC ENTRANCES SHALL BE ACCESSIBLE. |
| SEE THE EXCEPTIONS FOR ENTRANCES TO AREAS NOT REQUIRED |
| TO BE ACCESSIBLE AND LOADING/SERVICE ENTRANCES THAT ARE |
| NOT THE ONLY TENANT SPACE ENTRANCE. SHEET L1.01 SHOWS 4 |
| INCH STEP DOWN AT EACH EXIT. HOW IS ACCESSBLE ROUTE TO |
| BE PROVIDED, OR WHAT EXEMPTION ALLOWS FOR NO ACCESSIBLE |
| PATH TO BE PROVIDED? |
| |
| 6) 1013.1 FBC[B] SHEET L1.01 SHOWS AN EGRESS PATH GOING |
| THROUGH TWO EXISTING DOORS AND OUT THE BACK. |
| PLEASE USE EXIT SIGNS TO INDICATE EGRESS PATH. |
| |
| 7) 1017.2 FBC[B] LIMITATIONS. EXIT ACCESS TRAVEL |
| DISTANCE SHALL NOT EXCEED THE VALUES GIVEN IN TABLE |
| 1017.2. |
| |
| 8) 1017.3 FBC[B] MEASUREMENT. EXIT ACCESS TRAVEL |
| DISTANCE SHALL BE MEASURED FROM THE MOST REMOTE POINT |
| WITHIN A STORY ALONG THE NATURAL AND UNOBSTRUCTED PATH |
| OF HORIZONTAL AND VERTICAL EGRESS TRAVEL TO THE |
| ENTRANCE TO AN EXIT. |
| SHOW TRAVEL DISTANCE FROM THE MOST REMOTE POINT. |
| |
| 9) 107.3.5 FBC[AMENDED] SHOW THE EXISTING BATHROOMS ON |
| PLANS AND LABEL ROOMS ACCORDINGLY. |
| ALSO, SHOW ANY ADA COMPLIANCE THAT IS PROVIDED IN THE |
| BATHROOMS. |
| |
| NOTES: |
| |
| -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| EACH COMMENT IS BEING ADDRESSED. |
| |
| -COMMENTS ARE A BRIEF OVERVIEW OF CODE SECTIONS. |
| FURTHER REVIEW OF THE REFERENCED CODE SECTIONS WILL BE |
| REQUIRED. |
| |
| -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| OF MATERIALS REQUESTED. |
| |
| -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| NEED "VOID", RENDERING THEM NOT USABLE. |
| |
| PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| [email protected] |
| |
| |
| |