2019-03-06 16:52:41****CORRECTIONS****
 W.P.B. PERMIT: 19021325
 REVIEWED: MARCH 6, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 1) 301.1 FBC[EXISTING] GENERAL. THE REPAIR, ALTERATION,
 CHANGE OF OCCUPANCY, ADDITION OR RELOCATION OF ALL
 EXISTING BUILDINGS SHALL COMPLY WITH ONE OF THE METHODS
 LISTED IN SECTIONS 301.1.1 THROUGH 301.1.3 AS SELECTED
 BY THE APPLICANT. SECTIONS 301.1.1 THROUGH 301.1.3
 SHALL NOT BE APPLIED IN COMBINATION WITH EACH OTHER.
  WHICH METHOD IS BEING USED FOR COMPLIANCE?
 (PRESCRIPTIVE,WORK AREA OR PERFORMANCE)
  
 2) 501 FBC[EXISTING] STATE THE LEVEL OF ALTERATION FOR
 WORK BEING PERFORMED.
  THE PLANS STATE LEVEL 1, BUT THIS WOULD BE A LEVEL 2
 DUE TO THE RE-ARRANGEMENT OF SPACES AND POSSIBLE A
 LEVEL 3 IF OVER 50 % OF THE BUILDING IS INCLUDED IN THE
 WORK. PLEASE REVIEW AND REVISE TO MEET DEFINITION THAT
 APPLIES.
  
 3) 1004.1 FBC[B] DESIGN OCCUPANT LOAD. IN DETERMINING
 MEANS OF EGRESS REQUIREMENTS, THE NUMBER OF OCCUPANTS
 FOR WHOM MEANS OF EGRESS FACILITIES ARE PROVIDED SHALL
 BE DETERMINED IN ACCORDANCE WITH THIS SECTION.
  ADD OCCUPANT LOAD ON SHEET L1.01
  
 4) 302 FBC[B] WHAT IS THE EXISTING OCCUPANCY AND WHAT
 IS THE PROPOSED OCCUPANCY?
  PLEASE ADD TO SHEET L1.01
  
 5) 402.1 FBC[A] PROVIDE ACCESSIBLE ROUTE FROM PARKING
 LOT. IN ADDITION TO ACCESSIBLE ENTRANCES REQUIRED BY
 SECTIONS 1105.1.1 THROUGH 1105.1.7 (PARKING GARAGE
 ENTRANCES, ENTRANCES FROM TUNNELS OR ELEVATED WALKWAYS,
 RESTRICTED ENTRANCES, ENTRANCES FOR INMATES OR
 DETAINEES, SERVICE ENTRANCES AND ENTRANCES TO TENANT
 SPACES, DWELLING UNITS AND SLEEPING UNITS), AT LEAST 60
 PERCENT OF ALL PUBLIC ENTRANCES SHALL BE ACCESSIBLE.
 SEE THE EXCEPTIONS FOR ENTRANCES TO AREAS NOT REQUIRED
 TO BE ACCESSIBLE AND LOADING/SERVICE ENTRANCES THAT ARE
 NOT THE ONLY TENANT SPACE ENTRANCE. SHEET L1.01 SHOWS 4
 INCH STEP DOWN AT EACH EXIT. HOW IS ACCESSBLE ROUTE TO
 BE PROVIDED, OR WHAT EXEMPTION ALLOWS FOR NO ACCESSIBLE
 PATH TO BE PROVIDED?
  
 6) 1013.1 FBC[B] SHEET L1.01 SHOWS AN EGRESS PATH GOING
 THROUGH TWO EXISTING DOORS AND OUT THE BACK.
  PLEASE USE EXIT SIGNS TO INDICATE EGRESS PATH.
  
 7) 1017.2 FBC[B] LIMITATIONS. EXIT ACCESS TRAVEL
 DISTANCE SHALL NOT EXCEED THE VALUES GIVEN IN TABLE
 1017.2.
  
 8) 1017.3 FBC[B] MEASUREMENT. EXIT ACCESS TRAVEL
 DISTANCE SHALL BE MEASURED FROM THE MOST REMOTE POINT
 WITHIN A STORY ALONG THE NATURAL AND UNOBSTRUCTED PATH
 OF HORIZONTAL AND VERTICAL EGRESS TRAVEL TO THE
 ENTRANCE TO AN EXIT.
  SHOW TRAVEL DISTANCE FROM THE MOST REMOTE POINT.
  
 9) 107.3.5 FBC[AMENDED] SHOW THE EXISTING BATHROOMS ON
 PLANS AND LABEL ROOMS ACCORDINGLY.
  ALSO, SHOW ANY ADA COMPLIANCE THAT IS PROVIDED IN THE
 BATHROOMS.
  
 NOTES:
  
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
 -COMMENTS ARE A BRIEF OVERVIEW OF CODE SECTIONS.
 FURTHER REVIEW OF THE REFERENCED CODE SECTIONS WILL BE
 REQUIRED.
  
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
  
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  