Plan Review Notes
Plan Review Notes For Permit 19021254
Permit Number 19021254
Review Stop E
Sequence Number 2
Notes
Date Text
2019-04-18 08:40:22CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. RISER DIAGRAM SHOWS A NEW 100 AMP PANEL BEING FED
 WITH # 8 CONDUCTORS. IT SEEMS THE PLAN IS INDICATING
 THIS TO BE A PARALLEL FEED TO THE PANEL, ALTHOUGH THE
 TERMINOLOGY FOR PARALLEL FEEDS IS MISSING. PER NEC,
 PARALLEL CONDUCTORS ARE PERMITTED ONLY IS SIZES 1/0 AND
 LARGER. THE # 8 CONDUCTORS SHOWN IS NOT RATED FOR 100
 AMPS, PROVIDE CORRECTION. NEC 310.10(H); FBC RE E3401.2
 (PANEL SCHEDULE STILL SHOWS # 8 WIRES ON A 100 AMP
 BREAKER, RISER DIAGRAM SHOWS # 4 WIRE, BUT ONLY TWO
 WIRES. BOTH OF THESE WIRE SIZES ARE NOT RATED FOR 100
 AMPS. THERE SHOULD BE A TOTAL OF 4 WIRES IN THE CONDUIT
 FEEDING THIS PANEL, INCLUDING 2 HOT WIRES, A NEUTRAL,
 AND AN EQUIPMENT GROUNDING CONDUCTOR. PROVIDE
 CORRECTION.)
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3 (NOT PROVIDED)
 6. CORRECTED.
  
 NEW COMMENT:
  
 7. WHEN NEW PLAN SHEETS ARE BROUGHT IN FOR REVIEW, THE
 OLD SHEETS SHOULD BE REMOVED FROM THE SET AND THEN THE
 NEW SHEETS INSTALLED IN THE SET SO THAT THERE ARE 2
 COMPLETE SET OF PLANS. PROVIDE CORRECTION. WPB FBC
 107.1
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  