2019-04-18 08:40:22 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| |
| 1. RISER DIAGRAM SHOWS A NEW 100 AMP PANEL BEING FED |
| WITH # 8 CONDUCTORS. IT SEEMS THE PLAN IS INDICATING |
| THIS TO BE A PARALLEL FEED TO THE PANEL, ALTHOUGH THE |
| TERMINOLOGY FOR PARALLEL FEEDS IS MISSING. PER NEC, |
| PARALLEL CONDUCTORS ARE PERMITTED ONLY IS SIZES 1/0 AND |
| LARGER. THE # 8 CONDUCTORS SHOWN IS NOT RATED FOR 100 |
| AMPS, PROVIDE CORRECTION. NEC 310.10(H); FBC RE E3401.2 |
| (PANEL SCHEDULE STILL SHOWS # 8 WIRES ON A 100 AMP |
| BREAKER, RISER DIAGRAM SHOWS # 4 WIRE, BUT ONLY TWO |
| WIRES. BOTH OF THESE WIRE SIZES ARE NOT RATED FOR 100 |
| AMPS. THERE SHOULD BE A TOTAL OF 4 WIRES IN THE CONDUIT |
| FEEDING THIS PANEL, INCLUDING 2 HOT WIRES, A NEUTRAL, |
| AND AN EQUIPMENT GROUNDING CONDUCTOR. PROVIDE |
| CORRECTION.) |
| 2. CORRECTED. |
| 3. CORRECTED. |
| 4. CORRECTED. |
| 5. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS |
| LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND |
| VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS |
| IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC |
| 109.3 (NOT PROVIDED) |
| 6. CORRECTED. |
| |
| NEW COMMENT: |
| |
| 7. WHEN NEW PLAN SHEETS ARE BROUGHT IN FOR REVIEW, THE |
| OLD SHEETS SHOULD BE REMOVED FROM THE SET AND THEN THE |
| NEW SHEETS INSTALLED IN THE SET SO THAT THERE ARE 2 |
| COMPLETE SET OF PLANS. PROVIDE CORRECTION. WPB FBC |
| 107.1 |
| |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| SHEETS. |
| |