| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. RISER DIAGRAM SHOWS A NEW 100 AMP PANEL BEING FED |
| WITH # 8 CONDUCTORS. IT SEEMS THE PLAN IS INDICATING |
| THIS TO BE A PARALLEL FEED TO THE PANEL, ALTHOUGH THE |
| TERMINOLOGY FOR PARALLEL FEEDS IS MISSING. PER NEC, |
| PARALLEL CONDUCTORS ARE PERMITTED ONLY IS SIZES 1/0 AND |
| LARGER. THE # 8 CONDUCTORS SHOWN IS NOT RATED FOR 100 |
| AMPS, PROVIDE CORRECTION. NEC 310.10(H); FBC RE E3401.2 |
| 2. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE, |
| INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF |
| SERVICE IS ADEQUATE. LOAD CALCULATION PROVIDED IS NOT |
| COMPLIANT WITH FBC RE FORMAT AND IS ILLEGIBLE. NEC |
| 215.2, 220, 408.30; FBC RE E3602.2 |
| 3. AFCI PROTECTION SHOWN IS NOT CODE COMPLIANT. ALL |
| BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- |
| AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY |
| ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, |
| DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, |
| HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS |
| SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND |
| POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH |
| AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC |
| 210.8, 210.12; FBC RE E3902; FBC EX 607.1.1 OR 801.1, |
| 801.2, OR 901.2 AS APPLICABLE. |
| 4. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC |
| 210.8(D); FBC RE E3902.10 |
| 5. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS |
| LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND |
| VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS |
| IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC |
| 109.3 |
| 6. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED |
| PER CODE. SMOKE ALARMS MUST BE INSTALLED AT LEAST 3 |
| FEET FROM BATHROOM DOOR, 3 FEET FROM CEILING FANS, AND |
| 3 FEET FROM ANY MECHANICAL DUCT. PROVIDE CORRECTIONS. |
| FBC RE R314.3(4), R315.1, NFPA 72:29.8.3.4 |
| |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| SHEETS. |
| |