2019-03-12 06:59:50 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. ELECTRICAL PLAN IS REQUIRED TO BE SIGNED BY THE |
| ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS |
| 471.003(2)(H); 471.025; WPB FBC 107.1 |
| |
| 2. PROVIDE UL OR OTHER NRTL LISTINGS FOR WIFI WAP'S AND |
| SPEAKERS. ONLY CAMERA AND SMART SWITCH LISTINGS HAVE |
| BEEN PROVIDED. PROVIDE CORRECTION. FBC 107.2.1 NEC |
| 90.7,110.2,110.3B |
| |
| 3. VALUE FOR PROJECT SEEMS LOW. PROVIDE COPY OF SIGNED |
| CONTRACT WITH SCOPE AND VALUE OF WORK, TO INCLUDE ALL |
| MATERIALS AND LABOR. SIGNED BY OWNER AND CONTRACTOR. |
| FBC 109.3 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |