Plan Review Notes For Permit 19021184 |
Permit Number |
19021184 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-03-15 14:48:29 | 1ST REVIEW FBC-2017 MECHANICAL | | REVISION #19021184 | | PERMIT #16120365 | | 3/15/19 | | | | CODES IN EFFECT: | | | | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) THE REVISED PLAN SHOWS A CHANGE IN THE AC SYSTEMS | | FROM 17 SEER TO 16 SEER, AND AC #1 HAS BEEN REDUCED | | FROM 5 TONS TO 4 TONS. ALSO THE HEAT STRIPS HAVE BEEN | | INCREASED FROM 5KW TO 10KW. PLEASE PROVIDE REVISED AC | | LOAD AND ENERGY CALCULATIONS- SECTION R403.6.1 FBC EC | | AND SECTION 107.2.1 WPB. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|