Plan Review Notes For Permit 19021184
Permit Number 19021184
Review Stop M
Sequence Number 1
Notes
Date Text
2019-03-15 14:48:291ST REVIEW FBC-2017 MECHANICAL
 REVISION #19021184
 PERMIT #16120365
 3/15/19
  
 CODES IN EFFECT:
  
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE REVISED PLAN SHOWS A CHANGE IN THE AC SYSTEMS
 FROM 17 SEER TO 16 SEER, AND AC #1 HAS BEEN REDUCED
 FROM 5 TONS TO 4 TONS. ALSO THE HEAT STRIPS HAVE BEEN
 INCREASED FROM 5KW TO 10KW. PLEASE PROVIDE REVISED AC
 LOAD AND ENERGY CALCULATIONS- SECTION R403.6.1 FBC EC
 AND SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  