Plan Review Notes
Plan Review Notes For Permit 19021070
Permit Number 19021070
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2019-06-10 12:46:30THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET ALS 1.1 - IT APPEARS THAT THE FRONT DOORS ON
 THE SOUTH BAR AREA HAVE BEEN CLOSED OFF, LEAVING ONLY
 ONE EXIT FROM THAT BAR AREA, TOW EXITS ARE REQUIRED.
  
 PER NFPA 101 CH 12 & 7
  
 12.2.4* NUMBER OF MEANS OF EGRESS.
 12.2.4.1 THE NUMBER OF MEANS OF EGRESS SHALL BE IN
 ACCORDANCE
 WITH SECTION 7.4, OTHER THAN EXITS FOR FENCED OUTDOOR
 ASSEMBLY
 OCCUPANCIES IN ACCORDANCE WITH 12.2.4.4.
  
 7.4* NUMBER OF MEANS OF EGRESS.
 7.4.1 GENERAL.
 7.4.1.1 THE NUMBER OF MEANS OF EGRESS FROM ANY BALCONY,
 MEZZANINE, STORY, OR PORTION THEREOF SHALL BE NOT LESS
 THAN TWO,
 EXCEPT UNDER ONE OF THE FOLLOWING CONDITIONS:
 (1) A SINGLE MEANS OF EGRESS SHALL BE PERMITTED WHERE
 PERMITTED
 IN CHAPTERS 11 THROUGH 43.
 (2) A SINGLE MEANS OF EGRESS SHALL BE PERMITTED FOR A
 MEZZANINE
 OR BALCONY WHERE THE COMMON PATH OF TRAVEL LIMITATIONS
 OF
 CHAPTERS 11 THROUGH 43 ARE MET.
  
 ONE EXIT IS NOT ALLOWED IN CH 12.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE
 REFERENCES.
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  