Plan Review Notes For Permit 19021070 |
Permit Number |
19021070 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-04-08 10:55:36 | PLUMBING 1ST REVIEW**DENIED**BACKFLOW AND INTERCEPTOR | | SUB PERMIT REQUIRED**# 19021070 | | | | 1) PROVIDE NOTES ON PLUMBING SHT.P1.1.1 BACKFLOW AND | | INTERCEPTOR REQUIRED SEPERATE PLUMBING PERMITS. | | | | 2) TANKLESS WATER HEATER IS UNDERSIZED AND WILL NOT | | PROVIDE FIXTURES WITH HOT WATER. PROVIDE TANKLESS | | MANUFACTURES INSTALLATION MANUAL THAT WILL SUPPORT HOT | | WATER TO EACH FIXTURE. FBC-P 607.1 | | | | 3) SHOW RESTROOM FACUETS WATER WILL BE TEMPERED BY A | | ASSE 1070 DEVICE. FBC-P 607.1.2 | | | | 4) THE GREASE INTERCEPTOR SHALL BE REQUIRED TO HAVE 1 | | VENT THAT EXTENDS TO THE OUTDOORS. THE INTERCEPTOR | | SHALL NOT BE AIR BOUND AND AAV'S NOT NOT RATED FOR | | POSITIVE PRESSURE. FBC-P 904.1, 1003.2 | | | | 5) PLAN IS MISSING THE REQUIRED SERVICE SINK. FBC-P | | 403.1 | | | | 6) THE WATER SUPPLY DROPS ARE MISSING THE SHUT OFF | | SERVICE VALVES. FBC-P 606.1 | | | | 7) PROVIDE COMPLETE INSTALLATION MANUAL FOR THE GREASE | | INTERCEPTOR AND BOTH TANKLESS WATER HEATERS. FBC | | 107.2.1 | | | | | | TIM HUNT | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | CITY OF WEST PALM BEACH | | 561-248-2703 | | [email protected] | | [email protected] | | |
|