Plan Review Notes For Permit 19021070
Permit Number 19021070
Review Stop P
Sequence Number 1
Notes
Date Text
2019-04-08 10:55:36PLUMBING 1ST REVIEW**DENIED**BACKFLOW AND INTERCEPTOR
 SUB PERMIT REQUIRED**# 19021070
  
 1) PROVIDE NOTES ON PLUMBING SHT.P1.1.1 BACKFLOW AND
 INTERCEPTOR REQUIRED SEPERATE PLUMBING PERMITS.
  
 2) TANKLESS WATER HEATER IS UNDERSIZED AND WILL NOT
 PROVIDE FIXTURES WITH HOT WATER. PROVIDE TANKLESS
 MANUFACTURES INSTALLATION MANUAL THAT WILL SUPPORT HOT
 WATER TO EACH FIXTURE. FBC-P 607.1
  
 3) SHOW RESTROOM FACUETS WATER WILL BE TEMPERED BY A
 ASSE 1070 DEVICE. FBC-P 607.1.2
  
 4) THE GREASE INTERCEPTOR SHALL BE REQUIRED TO HAVE 1
 VENT THAT EXTENDS TO THE OUTDOORS. THE INTERCEPTOR
 SHALL NOT BE AIR BOUND AND AAV'S NOT NOT RATED FOR
 POSITIVE PRESSURE. FBC-P 904.1, 1003.2
  
 5) PLAN IS MISSING THE REQUIRED SERVICE SINK. FBC-P
 403.1
  
 6) THE WATER SUPPLY DROPS ARE MISSING THE SHUT OFF
 SERVICE VALVES. FBC-P 606.1
  
 7) PROVIDE COMPLETE INSTALLATION MANUAL FOR THE GREASE
 INTERCEPTOR AND BOTH TANKLESS WATER HEATERS. FBC
 107.2.1
  
  