2019-04-09 14:23:081ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19021070
 4/9/2019
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 RTU-1 SYSTEM- SECTION C403.2.1 FBC EC
  
 2) SHEET M1.1.1: A DUCT SMOKE DETECTOR IS REQUIRED IN
 THE SUPPLY AIR SYSTEM OF THE 5-TON RTU PER SECTION
 606.2.1. PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED
 IF THE MANUFACTURER'S SPECIFICATIONS INDICATE THE
 SYSTEM IS NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF
 SUPPLY AIR.
  
 3) M1.1.1 & M1.1.2: PROVIDE AN AUTOMATICALLY CONTROLLED
 SHUTOFF DAMPER FOR THE RTU OUTDOOR AIR INTAKE- SECTION
 C403.2.4.3 FBC-EC.
  
 4) M2.1.1: THE VENTILATION CALCULATIONS ARE NOT IN
 COMPLIANCE WITHTABLE 403.3.1.1 FBC M. THE RATE IS
 CALCULATED AT 100 PWRSONS PER 1000 SF. AT 7.5 CFMS PER
 PERSON + 0.18 CFMS PER SF. PLEASE CORRECT.
  
 5) M1.1.2: STRUCTURAL ENGINEERING IS REQUIRED FOR THE
 NEW ROOF OPENING, AND INSTSALLATIONS OF THE NEW CURB
 AND RTU- SECTION 301.15 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  