2019-04-09 14:23:08 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #19021070 |
| 4/9/2019 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW |
| RTU-1 SYSTEM- SECTION C403.2.1 FBC EC |
| |
| 2) SHEET M1.1.1: A DUCT SMOKE DETECTOR IS REQUIRED IN |
| THE SUPPLY AIR SYSTEM OF THE 5-TON RTU PER SECTION |
| 606.2.1. PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED |
| IF THE MANUFACTURER'S SPECIFICATIONS INDICATE THE |
| SYSTEM IS NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF |
| SUPPLY AIR. |
| |
| 3) M1.1.1 & M1.1.2: PROVIDE AN AUTOMATICALLY CONTROLLED |
| SHUTOFF DAMPER FOR THE RTU OUTDOOR AIR INTAKE- SECTION |
| C403.2.4.3 FBC-EC. |
| |
| 4) M2.1.1: THE VENTILATION CALCULATIONS ARE NOT IN |
| COMPLIANCE WITHTABLE 403.3.1.1 FBC M. THE RATE IS |
| CALCULATED AT 100 PWRSONS PER 1000 SF. AT 7.5 CFMS PER |
| PERSON + 0.18 CFMS PER SF. PLEASE CORRECT. |
| |
| 5) M1.1.2: STRUCTURAL ENGINEERING IS REQUIRED FOR THE |
| NEW ROOF OPENING, AND INSTSALLATIONS OF THE NEW CURB |
| AND RTU- SECTION 301.15 FBC M. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |
| [email protected] |
| |