2019-03-18 15:12:43PLUMBING 1ST REVIEW PERMIT # 19020927**DENIED**
  
 1) SHT A2 CALLS OUT GRAB BARS TO BE MOUNTED 33"-36" TO
 THE CENTER LINE OF THE BAR.GRAB BARS SHALL BE INSTALLED
 IN A HORIZONTAL POSITION, 33 INCHES (840 MM) MINIMUM
 AND 36 INCHES (915 MM) MAXIMUM ABOVE THE FINISH FLOOR
 MEASURED TO THE TOP OF THE GRIPPING SURFACE FBC-ACC
 609.4\
  
 2) SHOW PAPER DISPENSER 7"-9" FROM THE FRONT OF THE
 TOILET. FBC-ACC 604.9.6
  
 3)IS IT YOUR INTENT TO MAKE ALL FIXTURE AND RESTROOMS
 COMPLY WITH THE FLORIDA ACCESSIBILITY? SHT.T1 UNDER
 GENERAL NOTES E) CODE NOTES #8 CALLS FOR ALL FIXTURES
 AND HARDWARE TO COMPLY WITH ADA/ FBC-ACC. FBC 107.2.1
  
 4) PROVIDE COMPLETE BATHROOM LAY OUT SHOWING CLEAR
 FLOOR SPACE FOR BOTHT THE TOILET AND SINK COMPLYING
 WITH FBC-ACC604.3.2, 604.8.1.6
  