Plan Review Notes
Plan Review Notes For Permit 19020927
Permit Number 19020927
Review Stop B
Sequence Number 1
Notes
Date Text
2019-03-11 15:04:122017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19020927
 ADD: 4100 S DIXIE HWY. SUITE: B
 CONT: LEIGHTON MCGINN CO.
 TEL: 561-863-4455
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MONDAY / MARCH 11/ 2019
 ACTION: DENIED
 1) IT APPEARS THE SUBMITTED PLANS WERE ORIGINALLY PAPER
 PLANS THAT WERE CONVERTED TO DIGITAL PLANS, NONE OF THE
 DESIGNER OF RECORD SIGNATURE AND SEAL ARE DIGITAL
 SIGNATURE AND SEAL.
 ARCHITECTS: FLORIDA ADMINISTRATIVE CODE 61G1-16.005.
 PROCEDURES FOR DIGITALLY SIGNING AND SEALING AND FOR
 ELECTRONICALLY TRANSMITTING PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
  
 2) SHEET 004_A2 THE WATER CLOSET DETAIL SHOWS THE GRAB
 BARS BEING MEASURED FROM THE CENTERLINE OF THE GRAB BAR
 TO FINISH FLOOR. PLEASE NOTE UNDER THE 2017
 FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION OF GRAB
 BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE, NOT CENTERLINE.
  
 3) SHEET 005_A3 SHOWS AN OPEN SHELF THE BOTTOM AT 56
 INCHES OR 4 FOOT 8 INCHES ABOVE THE FINISH FLOOR, IT
 APPEARS TO BE FOR A MICROWAVE. SHEET 006_E1 THE POWER
 PLAN SHOWS AN OUTLET AT 72 INCHES FOR A MICROWAVE
 MACHINE. WITH A MICROWAVE PLACED IN THIS POSITION
 COMPLIANCE CAN NOT BE ACHIEVED FOR CODE SECTIONS, 2017
 FBC-ACCESSIBILITY CODE:
  
 308 REACH RANGES. 308.2 FORWARD REACH./ 308.2.1
 UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH.
 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2
 OBSTRUCTED HIGH REACH.
  
 309 OPERABLE PARTS. 309.3 HEIGHT. OPERABLE PARTS SHALL
 BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES
 SPECIFIED IN 308. 309.4 OPERATION. OPERABLE PARTS SHALL
 BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT
 GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE
 REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS
 MAXIMUM.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  