Text |
2019-03-11 15:04:12 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 19020927 |
| ADD: 4100 S DIXIE HWY. SUITE: B |
| CONT: LEIGHTON MCGINN CO. |
| TEL: 561-863-4455 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: MONDAY / MARCH 11/ 2019 |
| ACTION: DENIED |
| 1) IT APPEARS THE SUBMITTED PLANS WERE ORIGINALLY PAPER |
| PLANS THAT WERE CONVERTED TO DIGITAL PLANS, NONE OF THE |
| DESIGNER OF RECORD SIGNATURE AND SEAL ARE DIGITAL |
| SIGNATURE AND SEAL. |
| ARCHITECTS: FLORIDA ADMINISTRATIVE CODE 61G1-16.005. |
| PROCEDURES FOR DIGITALLY SIGNING AND SEALING AND FOR |
| ELECTRONICALLY TRANSMITTING PLANS, SPECIFICATIONS, |
| REPORTS OR OTHER DOCUMENTS. |
| |
| 2) SHEET 004_A2 THE WATER CLOSET DETAIL SHOWS THE GRAB |
| BARS BEING MEASURED FROM THE CENTERLINE OF THE GRAB BAR |
| TO FINISH FLOOR. PLEASE NOTE UNDER THE 2017 |
| FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION OF GRAB |
| BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL |
| POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE |
| THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING |
| SURFACE, NOT CENTERLINE. |
| |
| 3) SHEET 005_A3 SHOWS AN OPEN SHELF THE BOTTOM AT 56 |
| INCHES OR 4 FOOT 8 INCHES ABOVE THE FINISH FLOOR, IT |
| APPEARS TO BE FOR A MICROWAVE. SHEET 006_E1 THE POWER |
| PLAN SHOWS AN OUTLET AT 72 INCHES FOR A MICROWAVE |
| MACHINE. WITH A MICROWAVE PLACED IN THIS POSITION |
| COMPLIANCE CAN NOT BE ACHIEVED FOR CODE SECTIONS, 2017 |
| FBC-ACCESSIBILITY CODE: |
| |
| 308 REACH RANGES. 308.2 FORWARD REACH./ 308.2.1 |
| UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH. |
| 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2 |
| OBSTRUCTED HIGH REACH. |
| |
| 309 OPERABLE PARTS. 309.3 HEIGHT. OPERABLE PARTS SHALL |
| BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES |
| SPECIFIED IN 308. 309.4 OPERATION. OPERABLE PARTS SHALL |
| BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT |
| GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE |
| REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS |
| MAXIMUM. |
| |
| 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |