2019-03-15 10:45:44BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 JOSEAN A. DUPREY E.I., BN, PX
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6716
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
  
 1. THE WINDOW LOAD CHART IS NOT SIGNED BY THE ENGINEER.
 PLEASE RE-SUBMIT WITH A VALID DIGITAL SIGNATURE. FBC
 107
  
 2. THE GLASS TYPE INDICATED DO NOT MEET THE WIND LOAD
 PRESSURE REQUIRED ON THE WIND LOAD CHART. PLEASE HAVE
 THE ENGINEER SIGN THE WIND LOAD CHART AND INDICATE THE
 EXTERIOR WIND PRESSURE. THEN VERIFY THE PRODUCT AND
 GLASS TYPE SUBMITTED TO MEET THE REQUIRED EXTERIOR WIND
 PRESSURES. FBC 107
  