Plan Review Notes
Plan Review Notes For Permit 19020894
Permit Number 19020894
Review Stop P
Sequence Number 1
Notes
Date Text
2019-02-21 07:29:2802/21/19 1ST PLUMBING/BACKFLOW REVIEW **DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ALL BACKFLOW DEVICES MUST BE LEAD-FREE. LEAD-FREE
 (LF) SHALL BE INCLUDED IN THE SERIAL NUMBER OR STAMPED
 ON THE BODY OF THE DEVICE. ANY DEVICE THAT HAS BEEN
 ALTERED AFTER BEING ASSEMBLED BY THE MANUFACTURER WILL
 NOT BE APPROVED.
  
 2. TWO COPIES OF THE MANUFACTURER'S SPECIFICATIONS FOR
 THE BACKFLOW PREVENTER. THE MAKE, MODEL, AND SIZE OF
 THE DEVICE SHALL BE LISTED IN THE DESCRIPTION OF WORK
 SECTION ON THE PERMIT APPLICATION.
  
 3. DOCUMENTATION THAT THE PROPOSED DEVICE IS LEAD-FREE.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  
  