2019-03-18 16:14:39PLUMBING 1ST REVIEW PERMIT # 19020880**DENIED**
  
 THIS BUILDING AND UNIT WAS BUILD IN 2006 COMPLYING WITH
 THE FAIR HOUSING MANUAL (FHA). THE UNIT MUST CONTINUE
 TO COMPLY / BE ADAPTABLE WITH THE FAIR HOUSING MANUAL.
 PLEASE CONTACT PLAN REVIEWER FOR POSSIBLE ALTERNATIVE
 METHOD.
  
 1) CALL OUT ON PLAN WHAT FHA DESIGN SPEC EACH BATHROOM
 COMPLIES WITH. FBC 107.2.1
  
 2) SHOW EACH FIXTURE CLEAR FLOOR SPACE AS REQUIRED BY
 FHA. FBC 107.2.1
  
 3) PROVIDE CABINET DRAWING SHOWING EACH REQUIRED FHA
 SINK MAX 34" COMPLYING WITH FHA 7.52
  
 4) SHT A1 LIST THE BUILDING CODE AS 2007. AS OF DEC,31,
 2017 THE CODE IN AFFECT IS THE 2017 6TH ED. FBC 107.1
  
 5) PROVIDE INSTALLATION MANUAL FOR TUB VALVE SHOWING IT
 MEETS FBC-P 424.5 BY LIMITING TEMP TO 120F OR WHERE THE
 1070 DEVICE WILL BE LOCATED.
  
 6) PROVIDE SHOWER PAN DETAIL. FBC-P 107.2.1
  
 TIM HUNT
 PLUMBING INSPECTOR/PLUMBING PLAN EXAMINER