Plan Review Notes For Permit 19020880 |
Permit Number |
19020880 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-03-18 16:14:39 | PLUMBING 1ST REVIEW PERMIT # 19020880**DENIED** | | | | THIS BUILDING AND UNIT WAS BUILD IN 2006 COMPLYING WITH | | THE FAIR HOUSING MANUAL (FHA). THE UNIT MUST CONTINUE | | TO COMPLY / BE ADAPTABLE WITH THE FAIR HOUSING MANUAL. | | PLEASE CONTACT PLAN REVIEWER FOR POSSIBLE ALTERNATIVE | | METHOD. | | | | 1) CALL OUT ON PLAN WHAT FHA DESIGN SPEC EACH BATHROOM | | COMPLIES WITH. FBC 107.2.1 | | | | 2) SHOW EACH FIXTURE CLEAR FLOOR SPACE AS REQUIRED BY | | FHA. FBC 107.2.1 | | | | 3) PROVIDE CABINET DRAWING SHOWING EACH REQUIRED FHA | | SINK MAX 34" COMPLYING WITH FHA 7.52 | | | | 4) SHT A1 LIST THE BUILDING CODE AS 2007. AS OF DEC,31, | | 2017 THE CODE IN AFFECT IS THE 2017 6TH ED. FBC 107.1 | | | | 5) PROVIDE INSTALLATION MANUAL FOR TUB VALVE SHOWING IT | | MEETS FBC-P 424.5 BY LIMITING TEMP TO 120F OR WHERE THE | | 1070 DEVICE WILL BE LOCATED. | | | | 6) PROVIDE SHOWER PAN DETAIL. FBC-P 107.2.1 | | | | TIM HUNT | | PLUMBING INSPECTOR/PLUMBING PLAN EXAMINER | | BUILDING DIVISION | | CITY OF WEST PALM BEACH | | 561-248-2703 | | [email protected] | | |
|