Plan Review Notes
Plan Review Notes For Permit 19020860
Permit Number 19020860
Review Stop ENG
Sequence Number 1
Notes
Date Text
2019-02-22 07:31:02PASSED WITH PROVISOS:
  
 THE OPENING OF THE DUMPSTER ENCLOSURE MUST BE ANGLED SO
 THAT A 40 FT. LONG SANITATION TRUCK WITH THE FORKS
 EXTENDED CAN APPROACH THE OPENING AND PICK UP THE
 DUMPSTER WITHOUT MAKING A SHARP TURN OR A 3 POINT TURN.
  
 THE SANITATION TRUCK NEEDS TO HAVE NO LESS THAN 16 FT.
 HIGH VERTICAL CLEARANCE AREA FOR THE TRUCK TO PICK UP
 THE DUMPSTER. THIS IS THE CLEAR AREA OVER THE DUMPSTER
 AND WHERE THE TRUCK WILL BE STOPPED TO UNLOAD THE
 DUMPSTER.
  
 THE SANITATION TRUCK NEEDS TO HAVE NO LESS THAN 14 FT.
 HIGH VERTICAL CLEARANCE AND 12 FT. HORIZONTAL
 CLEARANCES FOR THE TRUCKS TO DRIVE THROUGH.
  
 IT IS STRONGLY SUGGESTED THAT YOU ADD A RECYCLING
 CENTER TO YOUR DUMPSTER ENCLOSURE.
  
 NO FLOOR DRAIN TO THE SANITARY SEWER CAN BE INSTALLED
 IN THE DUMPSTER ENCLOSURE, UNLESS IT IS ROOFED SO NO
 RAIN WATER WILL GET INTO THE DRAIN.
  
 THE DUMPSTER ENCLOSURE MUST BE LOCATED TO ALLOW THE
 SANITATION TRUCK TO BACK UP NO MORE THAN 50 FT.
 STRAIGHT BACK AFTER THE RESETTING OF THE DUMPSTER IN
 THE ENCLOSURE.
  
 DUMPSTER LOADING AREA SHALL HAVE 10' CONCRETE SURFACE
 FOR TRUCK TO APPROACH. TYPICALLY ASPHALT IS USED IN THE
 AREA APPROACHING THE DUMPSTER AND IT QUICKLY
 DETERIORATES DUE TO THE FRONT WHEELS OF THE SANITATION
 VEHICLE.
  
 THERE ARE WATER AND SEWER LINES IN THE VICINITY OF THIS
 PROJECT. PER CHAPTER 556 OF THE FLORIDA STATE STATUTES,
 YOU MUST CALL 811 FOR UTILITY LOCATES AT LEAST TWO FULL
 BUSINESS DAYS IN ADVANCE OF ANY CONSTRUCTION OR
 DEMOLITION WORK. MORE INFORMATION CAN BE FOUND HERE:
 HTTP://WWW.SUNSHINE811.COM/
  
 PLEASE SEE THE ENCLOSED LINK FOR A COPY OF THE CITY OF
 WEST PALM BEACH GENERAL CONSTRUCTION STANDARD DETAIL
 FOR DUMPSTER ENCLOSURES (GC-8). HTTP://WWW.WPB.ORG/DEPA
 RTMENTS/ENGINEERING-PUBLIC-WORKS/FORMS,-PERMITS-APPLICA
 TIONS
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO
 PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1098
 FAX: (561) 494-1116
 MOBILE: (561) 246-9525
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 MANNY GONZALEZ
 SENIOR ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 CENTRAL OPERATIONS CENTER (DISPATCH):
 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC
 UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved