2019-03-13 15:57:53 | MECHANICAL PLAN REVIEW |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| BUILDING PLANS EXAMINER, PX3169 |
| 1&2 FAMILY PLANS EXAMINER, SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 1ST REVIEW |
| RESULTS: DENIED |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. DESIGNERS SIGNATURE AND SEAL IS A COPY. |
| PLANS THAT HAVE BEEN PREPARED BY AN ENGINEER AND |
| SUBMITTED FOR PUBLIC RECORD SHALL BEAR THE SIGNATURE, |
| DATE AND SEAL OF THE ENGINEER PER FL ADMIN. CODE RULE |
| 61G15-23.001. |
| |
| 2. OWNER/AGENT TO SIGN ENERGY SUBMITTAL. |
| FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. |
| AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 |
| (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE |
| SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE |
| COMPLIANCE BY SECTION 405. |
| |
| 3. TAMPER RESISTANT PORT CAPS REQUIRED. |
| M1411.8 LOCKING ACCESS PORT CAPS. |
| REFRIGERANT CIRCUIT ACCESS PORTS LOCATED OUTDOORS SHALL |
| BE FITTED WITH LOCKING-TYPE TAMPER-RESISTANT CAPS OR |
| SHALL BE OTHERWISE SECURED TO PREVENT UNAUTHORIZED |
| ACCESS. |
| EXCEPTION: NO LOCKING-TYPE TAMPER-RESISTANT CAPS ARE |
| REQUIRED IF PORTS ARE LOCATED INSIDE THE CONDENSING |
| UNIT CABINET. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| REVIEWED SHEETS DETACHED. |
| |
| |
| |
| |
| |