Plan Review Notes
Plan Review Notes For Permit 19020771
Permit Number 19020771
Review Stop B
Sequence Number 1
Notes
Date Text
2019-03-28 13:18:12BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PROPERTY IS LOCATED IN A SPECIAL FLOOD HAZARD AREA
 (SFHA) WITH A BASE FLOOD ELEVATION (BFE) OF 12.1 FEET
 NAVD88.
  
 1. R322.2.5.1 POOLS LOCATED IN DESIGNATED FLOODWAYS.
 WHERE POOLS ARE LOCATED IN DESIGNATED FLOODWAYS,
 DOCUMENTATION SHALL BE SUBMITTED TO THE BUILDING
 OFFICIAL, WHICH DEMONSTRATES THAT THE CONSTRUCTION OF
 THE POOL WILL NOT INCREASE THE DESIGN FLOOD ELEVATION
 AT ANY POINT WITHIN THE JURISDICTION.
  
 2. EQUIPMENT TO BE INSTALLED PER FBC R322.1.6. NOTE:
 APPLICANT MAY PETITION THE BUILDING OFFICIAL TO INSTALL
 EQUIPMENT AT FINISHED FLOOR ELEVATION.
  
 3. DIGITAL SIGNATURES AND SEALS CANNOT BE VERIFIED.
  
 4. POOL BARRIER SHALL COMPLY WITH FBC R4502.17.1. DOOR
 AND WINDOW ALARMS REQUIRED.
  
 5. STAIR RISERS SHALL BE A MINUMUM OF 12 INCHES PER
 ANSI/APSP/ICC-5 2011.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  