2019-03-28 13:18:12 | BUILDING PLAN REVIEW |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| BUILDING PLANS EXAMINER, PX3169 |
| 1&2 FAMILY PLANS EXAMINER, SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 1ST REVIEW |
| RESULTS: DENIED |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| PROPERTY IS LOCATED IN A SPECIAL FLOOD HAZARD AREA |
| (SFHA) WITH A BASE FLOOD ELEVATION (BFE) OF 12.1 FEET |
| NAVD88. |
| |
| 1. R322.2.5.1 POOLS LOCATED IN DESIGNATED FLOODWAYS. |
| WHERE POOLS ARE LOCATED IN DESIGNATED FLOODWAYS, |
| DOCUMENTATION SHALL BE SUBMITTED TO THE BUILDING |
| OFFICIAL, WHICH DEMONSTRATES THAT THE CONSTRUCTION OF |
| THE POOL WILL NOT INCREASE THE DESIGN FLOOD ELEVATION |
| AT ANY POINT WITHIN THE JURISDICTION. |
| |
| 2. EQUIPMENT TO BE INSTALLED PER FBC R322.1.6. NOTE: |
| APPLICANT MAY PETITION THE BUILDING OFFICIAL TO INSTALL |
| EQUIPMENT AT FINISHED FLOOR ELEVATION. |
| |
| 3. DIGITAL SIGNATURES AND SEALS CANNOT BE VERIFIED. |
| |
| 4. POOL BARRIER SHALL COMPLY WITH FBC R4502.17.1. DOOR |
| AND WINDOW ALARMS REQUIRED. |
| |
| 5. STAIR RISERS SHALL BE A MINUMUM OF 12 INCHES PER |
| ANSI/APSP/ICC-5 2011. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| REVIEWED SHEETS DETACHED. |
| |
| |
| |
| |
| |