Plan Review Notes
Plan Review Notes For Permit 19020770
Permit Number 19020770
Review Stop P
Sequence Number 2
Notes
Date Text
2019-04-03 15:15:56PLUMBING 2ND REVIEW**DENIED**
  
 EXISTING COMMECTS
  
 1) NOT ADDRESSED. PROVIDE FLOOR PLAN DETIAL OF
 BATHROOMS SHOW REAR GRAB BAR 12" FROM THE CENTERLINE OF
 TOILET 36" IN OVERALL LENGHT. FBC-A 604.5.2
  
 2) ADDRESSED
  
 3) ADDRESS
  
 4) NOT ADDRESSED. TANKLESS WATER HEATERS WITH FACTORY
 PRE SET TEMP ARE NOT PREMITTED. FBC-P 607.1.1. UNIT
 EITHER SHALL HAVE A ASSE 1070 VALVE BUILT IN OR A 1070
 DEVICE ADDED TO COMPLY WITH FBC-P 607.1.2. THE MODEL
 SPEC ON PLANS DOES NOT MEET THE INTENT OF THE PLUMBING
 CODE.
  
 NEW COMMENT
  
 5) SIDE GRAB BAR IS SHOWING 11" OFF REAR WALL 42" IN
 LENGTH GIVING AN OVERALL OF 53". THE MIN DISTANCE FROM
 THE BACKWALL ALLOWED IS 54". SEE FBC-A 604.5.1 FOR
 DETAIL. YOUR BAR MUST BE MOUNTED @ 12" OFF BACKWALL TO
 COMPLY. SEE PLAN DETAIL SHT. A2.0
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
  