Plan Review Notes
Plan Review Notes For Permit 19020770
Permit Number 19020770
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2019-04-01 10:26:244/1/19
  
 THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1) SHEET E 1 0 - THERE ARE NO INDICATIONS OF FIRE ALARM
 DEVICES/EQUIPMENT WITHIN THE PAVILION.
  
 IF THERE IS AN EXITING FIRE SYSTEM WITHIN THE PAVILION,
 THE NEW RESTROOMS SHALL HAVE SYSTEM DEVICES EXTENDED
 INTO THEM.
  
 ANY WORK ON A FIRE ALARM SYSTEM SHALL BE DONE UNDER
 SEPARATE PERMITTED SHOP DRAWINGS BY CERTIFIED FIRE
 ALARM CONSTRACTORS.
  
 IF THERE IS NO FIRE ALARM SYSTEM IN THE PALVILION,
 PLEASE DISREGARD.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]