2020-03-17 14:13:09 | INCOMPLETE APPLICATION |
| |
| PERMIT 19020752 - UNDERGROUND FIBER MCIMETRO PROJECT |
| #1806CQCB.2 400 BLOCK OF HIBISCUS & GARDENIA |
| |
| PLEASE SEE THE LIST BELOW FOR AN ANALYSIS OF THE |
| DEFICIENCIES IN INFORMATION REQUIRED BY SECTION 78-401 |
| OF THE CITY OF WEST PALM BEACH CODE AS PART OF THE |
| COMMUNICATION FACILITIES PLACEMENT PERMIT APPLICATION. |
| THE DEFICIENT INFORMATION MUST BE PROVIDED FOR STAFF TO |
| REVIEW THE PERMIT APPLICATION. PLEASE NOTE THAT STAFF |
| HAS ALSO INCLUDED SOME SUBSTANTIVE REVIEW COMMENTS, |
| THAT WHILE NOT RESULTING IN A DEFICIENT APPLICATION, |
| NEED TO BE ADDRESSED OR THE PERMIT WILL NOT BE |
| APPROVED. |
| |
| 1) UPDATED COMMENT: SURVEY - THE SURVEY DOES NOT SHOW |
| SUFFICIENT INFORMATION FOR STAFF TO VERIFY WHAT IS |
| SHOWN ON THE ENGINEERING PLANS. |
| |
| A. THE SURVEY MUST BE PROVIDED AT A LEGIBLE SCALE AND |
| CLEARLY SHOW THE RIGHT-OF-WAY LINE AND THE SIDEWALK. |
| |
| B. ALL UNDERGROUND UTILITIES NEED TO BE PROVIDED ON THE |
| SURVEY. IF THE BORE IS PROPOSED WITHIN FIVE (5) FEET OF |
| AN EXISTING UTILITY, YOU NEED TO PROVIDE A LETTER FROM |
| THAT UTILITY THAT THE PROPOSED BORE DOES NOT INTERFERE |
| WITH THE PROVISIONS OF THEIR SERVICES. |
| |
| C. THE LOCATIONS OF THE TREES AND THEIR ROOT ZONE NEED |
| TO BE SHOWN. THE FIBER BORE NEEDS TO BE CLEARLY SHOWN |
| AVOIDING DAMAGE TO THE ROOT ZONES (THIS MAY OCCUR ON |
| THE ENGINEERING PLAN). |
| |
| D. THE ENGINEERING PLANS MUST SHOW THE SAME CONDITIONS |
| AS THE SURVEY, SO THAT STAFF CAN VERIFY THAT NONE OF |
| THE PROPOSED WORK IS BEING INSTALLED ON PRIVATE |
| PROPERTY. |
| |
| 2) REPEAT COMMENT: TIMETABLE - YOU ARE REQUIRED TO |
| PROVIDE THE ESTIMATED TIMETABLE FOR CONSTRUCTION OF THE |
| PROJECT OR EACH PHASE THEREOF. |
| |
| 3) REPEAT COMMENT: EVIDENCE OF INSURANCE COVERAGE - THE |
| CERTIFICATE OF LIABILITY INSURANCE NEEDS TO BE REVISED |
| TO NAME THE CITY OF WEST PALM BEACH, ITS COMMISSIONERS, |
| OFFICERS, EMPLOYEES AND AGENTS AS ADDITIONAL INSURED. |
| |
| 4) POLE STYLE - PLEASE NOTE THAT THE FUTURE POLES ARE |
| REQUIRED TO MEET THE CITY CONCEALMENT STANDARDS |
| OUTLINED IN SECTION 78-411 OF THE CITY CODE. |
| |
| NOTE: STAFF WILL NOT APPROVE THE INSTALLATION OF A SIX |
| (6) FOOT TALL MARKER POLE ADJACENT TO THE HANDHOLES. IF |
| THE HANDHOLES NEED TO BE MARKED, THEN PROVIDE THE |
| INFORMATION ON THE HANDHOLE COVER. |
| |
| 5) ELECTRONIC FORMAT OF SUBMITTAL - A COPY OF ALL OF |
| THE SUBMITTAL MATERIAL MUST BE SUBMITTED IN ELECTRONIC |
| FORMAT. |
| |