Plan Review Notes
Plan Review Notes For Permit 19020751
Permit Number 19020751
Review Stop Z
Sequence Number 6
Notes
Date Text
2021-02-16 15:45:03DENIED
  
 PERMIT 19020751 - UNDERGROUND FIBER MCIMETRO PROJECT
 #1806CQCB.4 IRIS TO S. DIXIE 2/2021 RESUBMITTAL
  
 PROVIDE WRITTEN RESPONSE TO COMMENTS.
  
 1) ENGINEERING PLAN - THE REVISED BORE LOCATION
 INCLUDES NEW TIE IN 4+90. THIS TIE IN IS TOO CLOSE TO
 THE EXISTING PALM TREE WITHIN THE SOUTH DIXIE
 RIGHT-OF-WAY. IN ORDER TO AVOID DAMAGE TO THE ROOT ZONE
 OF THE PALM TREE, THE EDGE OF THE DISTURBED AREA FOR
 THE TIE IN AND THE BORE MUST BE CLEARLY SHOWN TO BE A
 MINIMUM OF SIX (6) FEET FROM THE EDGE OF THE UNPAVED
 PLANTING AREA AROUND THE TREE.
  
 PLEASE NOTE:
  
 THE INSTALLATION CONTRACTOR MUST CONTACT SUNSHINE 811
 TO VERIFY THE LOCATION OF ALL UTILITIES AND VERIFY ALL
 DEPTHS PRIOR TO CONSTRUCTION. ALL CITY UTILITIES MUST
 BE LOCATED BY SOFT DIG METHODS BEFORE STARTING THE
 WORK.
  
 THE RIGHT-OF-WAY USE PERMIT REQUIRES YOU TO PROVIDE A
 CERTIFICATE OF LIABILITY INSURANCE, WHICH IN ACCORDANCE
 WITH SECTION 78-406 OF THE CITY CODE SPECIFICALLY NAMES
 THE CITY OF WEST PALM BEACH, ITS COMMISSIONERS,
 OFFICERS, EMPLOYEES AND AGENTS AS ADDITIONAL INSURED.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  