Plan Review Notes
Plan Review Notes For Permit 19020751
Permit Number 19020751
Review Stop Z
Sequence Number 4
Notes
Date Text
2020-08-19 11:21:09INCOMPLETE APPLICATION
  
 PERMIT 19020751 - UNDERGROUND FIBER MCIMETRO PROJECT
 #1806CQCB.4 IRIS TO S. DIXIE 3RD RESUBMITTAL
  
 PROVIDE WRITTEN RESPONSE TO COMMENTS.
  
 PLEASE SEE THE LIST BELOW FOR AN ANALYSIS OF THE
 DEFICIENCIES IN INFORMATION REQUIRED BY SECTION 78-401
 OF THE CITY OF WEST PALM BEACH CODE AS PART OF THE
 COMMUNICATION FACILITIES PLACEMENT PERMIT APPLICATION.
 THE DEFICIENT INFORMATION MUST BE PROVIDED FOR STAFF TO
 REVIEW THE PERMIT APPLICATION. PLEASE NOTE THAT STAFF
 HAS ALSO INCLUDED SOME SUBSTANTIVE REVIEW COMMENTS,
 THAT WHILE NOT RESULTING IN A DEFICIENT APPLICATION,
 NEED TO BE ADDRESSED OR THE PERMIT WILL NOT BE
 APPROVED.
  
 SOUTH DIXIE HIGHWAY BETWEEN IRIS STREET AND LAKEVIEW
 AVENUE IS A CITY, NOT FDOT, RIGHT-OF-WAY, SO THE PERMIT
 NEEDS TO INCLUDE THE ENTIRE LENGTH AS WAS PREVIOUSLY
 SUBMITTED. PLEASE PROVIDE SHEET 14 SO THAT STAFF CAN
 COMPLETE THE REVIEW.
  
 THE LOCATION LISTED ON SHEET 2 IS FOR COCONUT CREEK,
 NOT THE CITY OF WEST PALM BEACH. PLEASE CORRECT.
  
 1) ENGINEERING PLAN -
  
 A. PROVIDE SHEET 14 TO SHOW THE ENTIRE PORTION OF THE
 WORK WITHIN CITY RIGHT-OF-WAY.
  
 B. THE LOCATIONS OF THE TREES WITHIN 20 FEET OF THE
 EXISTING AND PROPOSED HANDHOLES AND THE PROPOSED TIE
 INS NEED TO BE SHOWN ON THE ENGINEERING PLAN AND BASED
 OFF THE SURVEY. THE ENGINEERING PLAN NEEDS TO SHOW THE
 TREES AND A TEN (10) FOOT SETBACK FROM THE TREES TO THE
 HANDHOLES AND TIE INS IN ORDER TO PREVENT DAMAGE TO THE
 TREES OR THEIR ROOT ZONES FROM BOTH THE BORE AND THE
 HANDHOLE INSTALLATION. WHERE THE BORE IS SHOWN AT FIVE
 (5) FEET BELOW GRADE IT IS AT A SUFFICIENT DEPTH TO
 AVOID DAMAGING THE ROOT ZONES; HOWEVER, STAFF NEEDS TO
 BE ABLE TO REVIEW THE LOCATIONS WHERE IT TRANSITIONS UP
 TO THE HANDHOLES AND THE TIE INS TO VERIFY THAT THERE
 IS NO ROOT ZONE DAMAGE.
  
 2) SURVEY - THE SURVEY THAT WAS PROVIDED DOES NOT COVER
 THE ENTIRE SCOPE OF THE APPLICATION ALONG SOUTH DIXIE
 HIGHWAY.
  
 PLEASE NOTE:
  
 THE INSTALLATION CONTRACTOR MUST CONTACT SUNSHINE 811
 TO VERIFY THE LOCATION OF ALL UTILITIES AND VERIFY ALL
 DEPTHS PRIOR TO CONSTRUCTION. ALL CITY UTILITIES MUST
 BE LOCATED BY SOFT DIG METHODS BEFORE STARTING THE
 WORK.
  
 THE RIGHT-OF-WAY USE PERMIT REQUIRES YOU TO PROVIDE A
 CERTIFICATE OF LIABILITY INSURANCE, WHICH IN ACCORDANCE
 WITH SECTION 78-406 OF THE CITY CODE SPECIFICALLY NAMES
 THE CITY OF WEST PALM BEACH, ITS COMMISSIONERS,
 OFFICERS, EMPLOYEES AND AGENTS AS ADDITIONAL INSURED.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved