2020-08-19 11:32:13 | FAILED |
| |
| PERMIT 19020748 - UNDERGROUND FIBER MCIMETRO PROJECT |
| #1806CQCB.6 800 BLOCK OF CHASE - 3RD RESUBMITTAL |
| |
| PROVIDE WRITTEN RESPONSE TO COMMENTS. |
| |
| THE FOLLOWING ITEMS NEED TO BE ADDRESSED OR THE PERMIT |
| WILL NOT BE APPROVED. |
| |
| 1) ENGINEERING PLAN - |
| |
| A. STAFF HAS REVIEWED AN ELECTRICAL PERMIT FOR A |
| PROPOSED VERIZON WIRELESS FACILITY; HOWEVER, IT WAS ON |
| THE NORTHEAST CORNER OF THIS INTERSECTION, NOT THE |
| NORTHWEST CORNER AS INDICATED ON THESE PLANS. PLEASE |
| VERIFY THE POLE LOCATION IN CASE IT AFFECTS YOUR PLANS. |
| |
| B. OTHER FIBER PLANS THAT YOU HAVE SUBMITTED INCLUDE |
| THE NOTE THAT THE TREE GRATE/PLANTING AREA MAY NOT BE |
| USED TO ASSIST IN THE BORE. PLEASE INCLUDE THIS NOTE ON |
| THE PLANS WITH THIS PERMIT. |
| |
| C. THE BORE SHOWN AT THREE (3) FEET BELOW GRADE IS AT A |
| SUFFICIENT DEPTH SINCE THERE ARE NO TREES BETWEEN THE |
| HANDHOLES. |
| |
| PLEASE NOTE: |
| |
| THE INSTALLATION CONTRACTOR MUST CONTACT SUNSHINE 811 |
| TO VERIFY THE LOCATION OF ALL UTILITIES AND VERIFY ALL |
| DEPTHS PRIOR TO CONSTRUCTION. ALL CITY UTILITIES MUST |
| BE LOCATED BY SOFT DIG METHODS BEFORE STARTING THE |
| WORK. |
| |
| THE RIGHT-OF-WAY USE PERMIT REQUIRES YOU TO PROVIDE A |
| CERTIFICATE OF LIABILITY INSURANCE, WHICH IN ACCORDANCE |
| WITH SECTION 78-406 OF THE CITY CODE SPECIFICALLY NAMES |
| THE CITY OF WEST PALM BEACH, ITS COMMISSIONERS, |
| OFFICERS, EMPLOYEES AND AGENTS AS ADDITIONAL INSURED. |
| |