Plan Review Notes
Plan Review Notes For Permit 19020741
Permit Number 19020741
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-02-27 11:03:58THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) SHEET A 0.3 - TWO EXITS ARE INDICATED; HOWEVER, A
 SITE PLAN IS NOT PROVIDED SHOWING THAT THESE EXITS LEAD
 TO A PUBLIC WAY.
  
  
 PER NFPA 101, CH 7 MEANS OF EGRESS
  
 7.7 DISCHARGE FROM EXITS.
 7.7.1* EXIT TERMINATION. EXITS SHALL TERMINATE
 DIRECTLY, AT A PUBLIC
 WAY OR AT AN EXTERIOR EXIT DISCHARGE, UNLESS OTHERWISE
 PROVIDED IN
 7.7.1.2 THROUGH 7.7.1.4.
  
 PLEASE NSURE THAT THESE EXITS HAVE A CLEAR UNOBSTRUCTED
 PATH TO A PUBLIC WAY PER NFPA 101 CH 7 MEANS OF EGRESS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  