2019-02-24 14:50:46 | 1) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017 |
| FBC-FUEL GAS CODE SEC.304.1, 614.6 (CLOTHES DRYERS) OR |
| 2017 FBC-RES. SEC.G 2407.1 AND G2439.4 (CLOTHES |
| DRYERS). |
| |
| 2) SUBMIT TWO COPIES OF THE MANUFACTURER?S |
| SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, |
| NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND |
| 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES |
| SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS |
| FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT |
| THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES. |
| SEC.G2408.1. |
| |
| 3) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE |
| LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION |
| AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN |
| RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER |
| HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND |
| DRAWN. WPB AMEND. TO FBC SEC. 107.2.1. |
| |
| 4) PLAN SHOWS TOTAL BTU AT 263,00. MY CALCULATION IS |
| 262,000 BTU TOTAL. PLEASE REVISE TOTAL BTU'S |
| |
| 5) SUBMIT MANUFACTURER?S SPECIFICATIONS AND |
| INSTALLATION INSTRUCTIONS FOR THE PRESSURE REGULATORS. |
| REGULATORS INSTALLED ON THE EXTERIOR OF THE BUILDING |
| SHALL BE APPROVED FOR OUTDOOR INSTALLATION. IDENTIFY ON |
| THE SPECIFICATION SHEETS WHICH MODEL REGULATOR IS BEING |
| INSTALLED AND THE ORIFICE SIZE TO ENSURE THE REGULATOR |
| CAN ACCOMMODATE THE BTU LOAD THROUGH THE REGULATOR.2017 |
| FGC SEC.410.1, 2017 FBC-RES. SEC. G2421.1. ( IF |
| APPLICABLE ) |
| |
| 6) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES |
| USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE |
| PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM |
| THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE |
| DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL |
| GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1) |
| THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8, |
| G2413.1, G2413.2, & G2413.3. |
| |
| 7) SEPERATE PERMIT REQUIRED FOR ELECTRIC |
| |
| |
| |