2019-08-14 18:10:20REVIEWED REMOTELY BY TIM HUNT
  
 APPROVED BUT REDLINE COMMENTS ON SHT. P-101
  
 1) CONDENSATE SHALL NOT DISCHARGE INTO THE STORM OR
 SANITARY SEWER. IT SHALL DISCHARGE OUTSIDE ONTO THE
 GROUND WITHOUT CAUSING A NUISANCE.
 2) ALL BATHROOM FIXTURES SHALL BE INDIVIDUALLY VENTED
 AS PER THESE PLANS. THE MOP SINK IS NOT PERMITTED TO
 DISCHARGE INTO THE BATHROOM WET VENT OTHERWISE. FBC-PLB
 912.2.1, CITY OF WPB ORD.
  
  