Plan Review Notes For Permit 19020678 |
Permit Number |
19020678 |
|
Review Stop |
P |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2019-08-14 18:10:20 | REVIEWED REMOTELY BY TIM HUNT | | | | APPROVED BUT REDLINE COMMENTS ON SHT. P-101 | | | | 1) CONDENSATE SHALL NOT DISCHARGE INTO THE STORM OR | | SANITARY SEWER. IT SHALL DISCHARGE OUTSIDE ONTO THE | | GROUND WITHOUT CAUSING A NUISANCE. | | 2) ALL BATHROOM FIXTURES SHALL BE INDIVIDUALLY VENTED | | AS PER THESE PLANS. THE MOP SINK IS NOT PERMITTED TO | | DISCHARGE INTO THE BATHROOM WET VENT OTHERWISE. FBC-PLB | | 912.2.1, CITY OF WPB ORD. | | | | |
|