2019-04-03 08:21:52 | PLUMBING 1ST REVIEW**DENIED** |
| |
| 1) SEE BUILDING REVIEWERS COMMENTS REGARDING OCCUPANCY |
| AND OCCUPANCY LOAD. FBC 107.3.5 |
| |
| 2) BOTH PLUMBING SANITARY FLAT DRAWING ON SHT. P-101 |
| AND SANITARY ISOMETRIC ON SHT. P-301 SHOW'S WOMENS ADA |
| SHOWER AS DRY VENTED AND ARE NOT COMPLETED DRAWINGS FOR |
| THE MENS RESTROOM. FBC-P 912.2, FBC 107.3.5 |
| |
| 3) PROVIDE OVERALL DEVELOPED LENGHT OF THE HOT WATER |
| LINE FROM THE WATER HEATER TO THE FIXTURES. IF OVER 50' |
| DEVELOPED LENGTH A RECIRCULATION SYSTEM SHALL BE USED |
| AND PIPING INSULATED TO MIN 1" WALL. FBC-P 607.2, 607.5 |
| |
| 4) SHT. P-301 WATER ISOMETRIC IS MISSING THE VALVES ON |
| THE WOMENS ADA SHOWER, MENS URINAL, AND 2ND LAV SINK. |
| FBC-P 606.1 |
| |
| 5) PROVIDE A DRAIN PAN AND DRAIN LINE FOR THE WATER |
| HEATER ON SHT. P401. FBC -P504.7 |
| |
| 6) SHT.A-106 CALLS OUT FOR THE GRAB BARS IN DETAIL (B) |
| & (J) TO BE 33"-36" TO THE CENTER LINE OF THE GRAB BAR. |
| THE MEASUREMENT SHALL BE TO THE TOP OF THE GRIPPING |
| SURFACE AS CALL OUT IN FBC-A 609.4 |
| |
| 7) PROVIDE SHOWER VALVE AND HAND HELD INSTALLATION |
| HEIGHT DETAIL ON SHT. A-106. FBC 107.3.5 |
| |
| 8) PROVIDE PLAN SHOWING THE REQUIRED CLEAR FLOOR SPACES |
| AS REQUIRED IN THE FLORIDA ACCESSIBILITY CODE. IT |
| DOESNT APPEAR THAT THE ADA MENS AND WOMENS SHOWER WILL |
| HAVE THE REQUIRED CLEAR FLOOR SPACE AND THE ABILITY TO |
| TRANSFER TO THE SHOWER SEATS. PLEASE CLARIFY. FBC-A |
| SECTION 608, CHAPTER 2,3,6 |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |
| |