2019-04-09 11:52:23 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #19020678 |
| 4/9/19 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE |
| NEW HEAT PUMP IN ACCORDANCE WITH SECTION C403.2.1 FBC |
| EC. |
| |
| 2) SHEET M201: PROVIDE EXHAUST VENTILATION CALCULATIONS |
| FOR THE LOCKER AND TOILET ROOMS- TABLE 403.3.1.1 FBC M. |
| |
| 3) M101: PROVIDE A DUCT SMOKE DETECTOR IN THE SUPPLY |
| SYSTEM OF THE NEW AHU-1- SECTION 606.2.1 FBC M. |
| |
| 4) M101: SHOW THE WATER SERVICE POINTS OF CONNECTIONS |
| TO AHU-1 |
| |
| 5) PROVIDE A CONDENSATE DISPOSAL PLAN FOR AHU-1- |
| SECTION 307.2.1 FBC M. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |