2019-04-09 11:52:231ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19020678
 4/9/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW HEAT PUMP IN ACCORDANCE WITH SECTION C403.2.1 FBC
 EC.
  
 2) SHEET M201: PROVIDE EXHAUST VENTILATION CALCULATIONS
 FOR THE LOCKER AND TOILET ROOMS- TABLE 403.3.1.1 FBC M.
  
 3) M101: PROVIDE A DUCT SMOKE DETECTOR IN THE SUPPLY
 SYSTEM OF THE NEW AHU-1- SECTION 606.2.1 FBC M.
  
 4) M101: SHOW THE WATER SERVICE POINTS OF CONNECTIONS
 TO AHU-1
  
 5) PROVIDE A CONDENSATE DISPOSAL PLAN FOR AHU-1-
 SECTION 307.2.1 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  