Date Text
2019-07-31 17:19:19PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. THERE IS AN
 ARCHITECT'S TITLE BLOCK ON THE MECHANICAL PLANS. THE
 ARCHITECT IS REQUIRED TO SIGN AND SEAL THE MECHANICAL
 PLANS WITH HIS NAME IN THE TITLE BLOCK WHEN SUBMITTED
 FOR PUBLIC RECORD PER CHAPTER 481, FLORIDA STATUTES &
 61G1 FLORIDA ADMINISTRATIVE CODE.
  
 2) THE HEATING AND COOLING EQUIPMENT IS PROVIDED ON THE
 FLOOR PLANS ON SHEET NUMBER 3 AND NOT SPECIFIED ON THE
 MECHANICAL PLANS ON SHEET NUMBER 4 AS REQUESTED. THERE
 ARE TWO PLAN SHEETS IDENTIFIED AS SHEET NUMBER 4. FBC
 107.2.1 PROVIDE THE MODEL NUMBERS AND SPECIFICATIONS OF
 THE HEATING AND COOLING EQUIPMENT IN AN EQUIPMENT
 SCHEDULE ON THE MECHANICAL PLAN THAT CORRESPONDS WITH
 THE EQUIPMENT SIZING CALCULATIONS.
  