2019-06-17 12:32:27 | PLUMBING PROVISO: |
| 1) P2708.4SHOWER CONTROL VALVES. |
| INDIVIDUAL SHOWER AND TUB/ SHOWER COMBINATION VALVES |
| SHALL BE EQUIPPED WITH CONTROL VALVES OF THE |
| PRESSURE-BALANCE, THERMOSTATIC-MIXING OR COMBINATION |
| PRESSURE-BALANCE/THERMOSTATIC-MIXING VALVE TYPES WITH A |
| HIGH LIMIT STOP IN ACCORDANCE WITH ASSE 1016/ASME |
| A112.1016/CSA B125.16. THE HIGH LIMIT STOP SHALL BE SET |
| TO LIMIT THE WATER TEMPERATURE TO NOT GREATER THAN |
| 120?F (49?C). IN-LINE THERMOSTATIC VALVES SHALL NOT BE |
| USED FOR COMPLIANCE WITH THIS SECTION. |
| 2) P2709.3INSTALLATION. |
| LINING MATERIALS SHALL BE SLOPED ONEFOURTH UNIT |
| VERTICAL IN 12 UNITS HORIZONTAL (2-PERCENT SLOPE) TO |
| WEEP HOLES IN THE SUBDRAIN BY MEANS OF A SMOOTH, |
| SOLIDLY FORMED SUBBASE, SHALL BE PROPERLY RECESSED AND |
| FASTENED TO APPROVED BACKING SO AS NOT TO OCCUPY THE |
| SPACE REQUIRED FOR THE WALL COVERING, AND SHALL NOT BE |
| NAILED OR PERFORATED AT ANY POINT LESS THAN 1 INCH |
| (25.4 MM) ABOVE THE FINISHED THRESHOLD. |
| 3) P2801.6REQUIRED PAN. |
| WHERE A STORAGE TANK-TYPE WATER HEATER OR A HOT WATER |
| STORAGE TANK IS INSTALLED IN A LOCATION WHERE WATER |
| LEAKAGE FROM THE TANK WILL CAUSE DAMAGE |
| 4) P2801.6.2PAN DRAIN TERMINATION. |
| THE PAN DRAIN SHALL EXTEND FULL-SIZE AND TERMINATE OVER |
| A SUITABLY LOCATED INDIRECT WASTE RECEPTOR OR SHALL |
| EXTEND TO THE EXTERIOR OF THE BUILDING AND TERMINATE |
| NOT LESS THAN 6 INCHES (152 MM) AND NOT MORE THAN 24 |
| INCHES (610 MM) ABOVE THE ADJACENT GROUND SURFACE. |
| 5) P2804.6.1REQUIREMENTS FOR DISCHARGE PIPE. |
| THE DISCHARGE PIPING SERVING A PRESSURE-RELIEF VALVE, |
| TEMPERATURE RELIEF VALVE OR COMBINATION VALVE SHALL |
| DISCHARGE INTO THE ROOM THE WATER HEATER SERVES. |
| 6) WATER HEATER SHALL BE MIN .98E.F AS CALLED OUT IN |
| THE R405 ENERGY FORM. |
| |